background image

The preheating temperature for the anti-frost function in the heat recovery cell is
chosen with the + and – buttons.

3.3.24. Pre-heating temperature for the anti-frost function in the heat recovery cell

Preheater
07C

VALLOX 90 SE

INSTRUCTIONS FOR USING THE CONTROL PANEL

10

The hysteresis of the anti-frost function in the heat recovery cell is selected with the + and – buttons.

3.3.22.  Hysteresis of the anti-frost function in the heat recovery cell

Hysteresis
03C

The interval for the maintenance reminder is selected with the + and – buttons. The
maintenance reminder interval refers to months.

3.3.21. Choosing maintenance reminder interval

Maintenance rem.
04

A water or electric radiator is selected with the + and – buttons, depending on the type of post-
heating radiator the unit is equipped with.

Note! Choosing the wrong type of post-heating causes a faulty post-heating function.

3.3.20. Choosing post-heating for the unit

Radiator type
electric rad.

The basic humidity level can be chosen as either automatic or manual. The selection is
done with the + and – buttons.

3.3.19. Choosing the basic humidity level

Rh-level setting
automatic

The desired setpoint is chosen with the + and – buttons when manual adjustment has been selected
as the Rh level setting (humidity setting, section 3.3.19).

3.3.16. Setpoint of the basic humidity level

Basic %RH level
40%

The desired cell bypass temperature is selected with the + and – buttons. If outdoor temperature
is lower than cell bypass temperature, the summer / winter damper is in the winter position.

3.3.15.  Changing the operating temperature of heat recovery cell bypass

Cell bypass
10C

The desired adjustment value for the DC fan is selected with the + and – buttons. The rotation speed
of the supply air fan can be lowered by decreasing the percentage value. If the unit has alternating
current fans, this adjustment has no impact on the functioning of the unit.

3.3.14. Adjusting the direct current fan of the supply air side

DC fan - supply
100%

The mode of operation of the switch (either fireplace or booster switch) is selected
with the + and – buttons.

3.3.17. Mode of operation of the fireplace / booster switch

Switch type
Fireplace switch

Cascade control is activated or deactivated with the + and – buttons.

3.3.18. Choosing cascade control for supply air temperature

Cascade adjust
Off

The setpoint for CO

2

 adjustment is chosen with the + and – buttons.

3.3.25. Changing the setpoint for carbon dioxide adjustment

CO2-setting
0900 PPM

The desired maximum fan speed is selected with the + and – buttons. Maximum fan
speed is on either with adjustments or permanently. See section 3.3.6. Mode of
operation of the maximum speed setting.

3.3.26. Choosing maximum fan speed

MAX speed
8

The stopping temperature of the supply air fan for the anti-frost function in the heat
recovery cell is chosen with the + and – buttons.

3.3.23. Stopping temperature of the supply air fan for the anti-frost function in the heat recovery cell

Supply fan stop
05C

Содержание 90 SE L

Страница 1: ...AY 1 09 332E 10 4 2009 Code 3520 VALLOX Direct current fan model C326 05 INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX 90 SE R VALLOX 90 SE L CODE 3520 SUPPLY AND EXTRACT AIR VENTILATION WITH HEA...

Страница 2: ...90 SE L With direct current fans VTT certificate number Direct current fan model C326 05 Pre post heating radiator Preheating radiator electric max 900 W standard Post heating radiator electric max 90...

Страница 3: ...approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter...

Страница 4: ...eed Ventilation power cannot be set lower than the basic fan speed When carbon dioxide and or relative humidity adjustments are activated power cannot be adjusted higher than the maximum fan speed Whe...

Страница 5: ...speed In humidity control fan speed varies between the basic and maximum fan speeds selected When the unit is taken into use for the first time with automatic setpoint search selected factory setting...

Страница 6: ...1 Heat recovery bypass function The bypass function tries to get as cool supply air as possible to the ventilation zone by comparing the measuring results of the outdoor air and extract air sensors Th...

Страница 7: ...speed for 45 minutes The function is started at the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seconds The function can also be started at a s...

Страница 8: ...ttings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 Scrolling down With this button you c...

Страница 9: ...tment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance remin...

Страница 10: ...ure is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operating temperature of heat r...

Страница 11: ...lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finished by moving the cursor below the word Exi...

Страница 12: ...ff before it is possible to start removing the cell When the sealing ledge has been removed the HR cell can be pulled out of the unit Note The laminas of the HR cell are very thin and get easily damag...

Страница 13: ...ut Finally disconnect the quick coupling of the fan conductor Removing the extract air fan B The fan is attached to the fixing plate with a butterfly nut Loosen the butterfly nuts and lift the fan out...

Страница 14: ...n stop ping and starting See the instructions for using the control panel section 3 3 19 The maintenance reminder symbol is displayed and the unit operates otherwise normally The maintenance reminder...

Страница 15: ...l The door switch may be broken or the door is possibly not quite closed The unit is out of power e g because a fuse has blown The glass tube fuse located in the control card behind a protecting plate...

Страница 16: ...VALLOX We reserve the right to make changes without prior notification 1 09 332E 10 4 2009 PDF VALLOX 90 SE Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com...

Страница 17: ......

Отзывы: