MAINTENANCE INSTRUCTIONS

FANS

The supply and extract air fans (D and E) have been fastened with rubber
collars (F). When removing the fans for maintenance, release the ear (K) fixed
to the fan over the rubber collar (F) flange by turning the ear to the upright
position. Lift the rubber collar out of the opening and turn the fan so that it
can be lifted away from the support (M). Remove the plug (G) of the fan.

Cleaning the fans

Clean the fan blades with compressed air or with brush. Each blade has to
be so clean that the fans stay balanced. Take care not to unfasten the balancing
pieces attached to the fan blades.

If you use water in cleaning the unit or its parts, do not let it flow into the electrical parts.

Unfastening and fastening of the self-actuated one-way
damper (vacuum damper)

Y

K

F

B

Y

K

F

C

Y

K

F

A

T

Thermostat sensor has been unlocked. Detach the sensor by turning the collar to
the direction shown by the arrow.

When remounting the sensor, turn the collar to the direction shown by the arrow
to make the claws lock in the open position, check that the green indicator dot is
visible and push the thermostat sensor to attach it to the body of the valve.

Y

F

T

K

Thermostat part and one-way damper in the VKL model

Unfastening and fastening of the thermostat part of the self-actuated valve

A

B

C

Put the hook on the edge of the damper (Y) under the back edge
of the fastening collar (K) of the fan (F) and push the damper
down till the guiding edges of the valve go inside the rubber
collar.

Push the front edge of the collar with your finger.

Put the hook on the front edge of the damper below
the front edge of the collar.

When unfastening the damper, take the same steps in the opposite
order.
Self-actuated one-way dampers are only used in VKL model units.

CONDENSING WATER

During the heating season, humidity of extract air condenses to water. Water
formation may be abundant in new buildings or if ventilation is low compared
to the humidity build-up caused by the residents.

OTHER CLEANING

In connection with maintenance, also check the inner surface of the unit and the condensing
water reservoir. If they are dirty, clean them gently with a damp cloth, brush, vacuum cleaner
or similar. Keep the unit clean to ensure its flawless operation and hygiene.

Condensing water needs to flow out from the ventilation unit without hindrance. In connection
with maintenance, e.g. in autumn before the beginning of the heating season, make sure that
the condensing water outlet in the bottom reservoir is not clogged. You may check it by
pouring a little water in the reservoir.

Do not let water flow into electrical devices.

Содержание 75

Страница 1: ...INSTRUCTIONS FOR USE AND MAINTENANCE 1 09 292E 13 02 07 VALLOX For blocks of flats terraced houses and detached houses Supply and extract air ventilation with heat recovery Type 3510...

Страница 2: ...rying fa cilities during these activities Sleeping Ventilation in a bedroom has to be suffi cient throughout the night The level is cor rect when air does not smell fusty when you enter the room in th...

Страница 3: ...thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter water condenses in the cold structures of the house and mould starts to form The recommended maxi...

Страница 4: ...ered before taking it in to the dwelling A coarse filter first removes the biggest litter particles thereby preventing the system from getting dirty After that air passes through a fine filter which c...

Страница 5: ...during for example sauna baths cooking clothes washing or family parties If the user does not know the measured air flows the adjacent table shows approximate extract air flows as well as the total e...

Страница 6: ...toilet guests excess heat and large dwellings Speed 4 This boosting position is used as needed for example during cooking parties and hot weathers Cooking Open the flap of the cooker hood during cooki...

Страница 7: ...g supply air The temperature of supply air is adjusted at the thermostat regulator located inside the unit Adjustment range of temperature is approximately 0 25 C It is advisable to set the thermostat...

Страница 8: ...at at 0 C position so that the radiator will not heat If needed the setpoint value of the water radiator thermostat shall also be reduced Defrosting Water condensing from extract air may freeze in the...

Страница 9: ...filter material To ensure good supply air quality replace the filter from every six months toyear more often if needed depending on local air quality It is recommended to replace filters in autumn Thi...

Страница 10: ...amper in the VKL model Unfastening and fastening of the thermostat part of the self actuated valve A B C Put the hook on the edge of the damper Y under the back edge of the fastening collar K of the f...

Страница 11: ...he ceiling or the wall caused by the flow coming from the valve Cooker hood connected to the ventilation unit The most important object of maintenance is the grease filter To ensure sufficient absorpt...

Страница 12: ...outdoor temperatures no humidity no freezing you can move the sensor further away from the cell An expert may also adjust the thermostat in the connection box by turning its spindle clockwise to 10 C...

Страница 13: ......

Отзывы: