Vallox 3603 Скачать руководство пользователя страница 14

14

 

ELECTRIC

AL CONNECTIONS

EXTERNAL ELECTRICAL CONNECTION 

with Vallox ProControl control panel 

EXTERNAL ELECTRICAL CONNECTION 

with an external control panel 

Wiring between the control panel and the ventilation unit, NOMAK 2x2x0.5+0.5

Ventilation unit cable

Control panel connector

S

Y1

+

leave disconnected

-

G0

LED

S/DI2

CONTROL PANEL
G

24 VAC feed

S/DI2

Error relay

G0 0 VAC

G0

0 VAC

Y1

10 V, control voltage 

of the ventilation unit

Y2
DI1 Boost at the cooker hood
A1

24 VAC 1 A, intermediate 

relay control

Y3
A2
Y4
U1

0...10 V, humidity boost

A+ RS-485
B-

RS-485

C

RS-485 Common

RH%

optional 

946147

Nomak
2x2x0,5+0,5

0...10V

LED

G
G0
Y1
Y2
DI1
A1
Y3
A2
Y4
U1
A+
B-
C

S/DI2
G0

Vallox Procontrol

949034

S

LED

S

+

+

-

-

B term
CONFIG

Control signal S

Cooker hood 

or boost switch

11.2 VDC / +

GND / -

DISTRIBUTION 

BOARD

L  N

24V

Error relay / LED

Nomak 2x2x0,5+0,5

Modbus

RS-485

Nomak 

2x2x0,5+0,5

Cable types specified in the drawing are indicative

2x0.5

2x0.5

Internal connection 

of the ventilation unit

The phase of 24 VAC feed is connected 

to the control panel connector G and 

the neutral to the connector G0

Control signal S

GND / -

An external 0-10 VDC 

voltage can be 

connected to the S 

and GND connectors 

for fan control.

External control panel

S

S

+

+

-

-

GND / -

LED LED

Internal connection 

of the ventilation unit

Control signal S

11.2 VDC / +

Error relay / LED

Содержание 3603

Страница 1: ...Manual MANUAL Low energy ventilation unit with heat recovery Document D2585 Valid from 07 03 2022 Updated 20 06 2022 Model Vallox TSK Multi 50 MC Vallox TSK Multi 80 MC Types 3603 B3602...

Страница 2: ...er 8 or by persons with reduced sensory physical or mental capabilities or whose lack of knowledge and experience do not ensure safe operation of the unit Such persons can use the unit under supervisi...

Страница 3: ...post heating is turned off and the heat recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AU...

Страница 4: ...entiometer is turned clockwise the extract air flow is reduced The potentiometer for adjusting the supply and extract air flows Concealed installation of the fireplace switch optional MAINTENANCE REMI...

Страница 5: ...aintenance FILTERS When the maintenance reminder becomes activated check the cleanliness of the filters and replace them if required The Vallox ventilation unit has three air filters Coarse filter for...

Страница 6: ...OVERY CELL Check that the heat recovery cell D is clean roughly once a year when the filters are being replaced Clean by washing as required Pull the coarse filters including the frames out of the uni...

Страница 7: ...ass duct filter stand package out of the unit and turn to the right 3 Disconnect the cable of the bypass damper motor 4 Tilt the supply air fan to the right and push the connectors out of the way 5 Tu...

Страница 8: ...3 kW 0 32 A EC 0 043 kW 0 32 A EC Specific energy consumption SEC in a cold climate in a temperate climate A B Operating efficiencies Annual efficiency Supply air efficiency Specific Fan Power SFP 79...

Страница 9: ...74 77 250 47 55 62 66 68 69 71 73 73 39 47 55 60 61 62 63 65 67 500 36 44 50 55 59 63 66 68 70 26 33 38 42 47 52 55 57 57 1000 29 39 45 50 54 59 61 63 65 21 29 34 38 42 45 48 50 52 2000 21 29 39 45 5...

Страница 10: ...PM ISO Coarse 75 Heat recovery bypass Automatic Dimensions w x h x d and weight 1026 x 293 x 626 58 5 kg Working point defined in the Ecodesign Directive 2009 125 EC Southern Finland Helsinki Vantaa T...

Страница 11: ...22 36 42 51 60 66 67 Fre quency of the octave band Hz 63 60 67 68 72 73 79 79 78 54 58 59 63 66 78 70 73 125 56 65 64 66 68 70 72 73 48 56 54 56 58 62 63 64 250 51 58 67 70 74 78 76 76 43 50 61 59 61...

Страница 12: ...hood Cables BK black BN brown BU blue GN green GY grey WT white YE GN yellow green RD red 951155 951123 951153 951159 BU 1 BN 2 YEGN 9 951150 951152 BN 7 W T 8 GN 15 YE 16 RD 7 W T 8 BU 15 YE 16 BK 1...

Страница 13: ...CHO GND PWM DAMP IN OUT MODE IN OUT F ALARM RS 485 A B GND N L DAMPER 1 2 3 LIGHT N L FAN N L VDC VDC Tacho S MC VENTILATION UNIT five terminal connector GND S GND S MV VENTILATION UNIT GND AN I RM I...

Страница 14: ...RS 485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11...

Страница 15: ...ot cause any disturbance Such locations include storage premises and technical spaces Important The whole length of the outdoor air duct to the unit and exhaust air duct from the unit must be insulate...

Страница 16: ...942211 13 Side sealing strip of the heat recovery cell 3356300 Vallox TSK Multi 50 MC 13 Side sealing strip of the heat recovery cell 3352600 Vallox TSK Multi 80 MC NO Part Product number 14 Upper sea...

Отзывы: