The following approx. values must be obtained:
If different pressure values are obtained, an authorized repair shop must be consulted to investigate the
reasons.
When the pressure test is complete, disconnect the pressure gauges and refit the sealing caps.
6.8.2. Visual inspection
The system must be inspected visually as described in chapter 6.5 when the repairs are complete.
Outside air
temperature
=Indoor temperature
Low pressure gauge
High pressure gauge
62.60°F
2.7 ± 0.2 bar
8.4 ± 2 bar
68.00°F
2.9 ± 0.2 bar
9.0 ± 2 bar
77.00°F
3.3 ± 0.2 bar
10.3 ± 2 bar
86.00°F
4.1 ± 0.2 bar
11.4 ± 2 bar
95.00°F
4.7 ± 0.2 bar
12.8 ± 2 bar