Energy Core Ventilator

HOA Troubleshooting

ERV Troubleshooting Guide

Symptoms

Potential Issues

Fix

Unit is NOT operating

 

¦

Loss of Input Power

 

¦

Incorrect wiring

 

¦

Green LED is not

 

illuminated for Remote 

ON

 

¦

No contact closure

 

between Pins 1 & 2 

of TB2 for Remote 

ON”

 

¦

Check Breaker

 

¦

Check input power Wiring

 

¦

Validate correct Input Power to Terminal 
Block TB1

 

¦

Validate a short between Pins 1 & 2 of 
TB2 for Remote 

ON”

 

¦

Validate Green LED is illuminated for 
Remote ON

Energy Wheel Motor 

does not turn ON

 

¦

No contact closure between Pins 1 & 2 
of TB2 for Remote “ON”

 

¦

Validate Motor wiring to W5 and W6 
(1/4”) Spade Faston tabs on ERV 
Controller

 

¦

Validate Motor Wiring

 

¦

Validate Green LED on ERV Controller is 
illuminated 

ON

 

¦

Energy Wheel is stuck and is not free. 
Turn the energy recovery wheel by hand 
to verify free operation

 

¦

Replace motor

A Motor does not 

turn

 

ON

 

¦

No contact closure between Pins 1 & 
2 of TB2 for Remote 

ON

 

¦

Validate Motor wiring to W3 and W4 
(1/4

) Spade Faston tabs on ERV 

Controller

 

¦

Validate speed potentiometer is above 
>

 

2.0Vdc

 

¦

Validate Motor Wiring

 

¦

Validate 0-10V Motor command Voltage 
at Motor. Motor command voltage must 
be> than 2.00V

 

¦

Validate Frost control is not activated. 
Check SW1 Inlet/Outlet switch

B Motor does not 

turn

 

ON

 

¦

No contact closure between Pins 1 & 
2 of TB2 for Remote 

ON

 

¦

Validate Motor wiring to W1 and W2 
(1/4

) Spade Faston tabs on ERV 

Controller

 

¦

Validate speed potentiometer is above 
>

 

2.0Vdc

 

¦

Validate Motor Wiring

 

¦

Validate 0-10V Motor command Voltage 
at Motor. Motor command voltage must 
be> than 2

.

00V

 

¦

Validate Frost control is not activated 
Check SW1 Inlet/Outlet switch

No Frost Control

 

¦

Validate Thermostat Wiring Pins 5 and 6 
of TB2

 

¦

Validate Blue LED is Illuminated

 

¦

Inlet and Exhaust vents are swapped 
simply slide SW1 switch on ERV PCB A 
and B

 

motors to reverse setting

 

¦

Validate Frost control is not 
activated.

 

¦

Validate SW1 Inlet/Outlet switch is 
set correctly.

 

¦

Validate Timers T1 and T2 for 
correct settings

.

No 24V 

Sensor Power

 

¦

Check wiring to Pins 3 and 4 of TB2

.

 

¦

Measure Vo

l

tage at Pins 3 and 4 of 

TB2 for +24Vdc

 

¦

Check input power Wiring

 

¦

Validate correct Input Power to Terminal 
Block TB1

 

¦

Remove wires at Pins 3 and 4 of TB2 
and measure the voltage for +24Vdc. If 
+24Vdc is measured, there 

i

s too much 

current draw (sensor can be damaged or 
drawing too much

 

power) Check Breaker

Содержание ERC-M

Страница 1: ...d 1 Follow all local electrical and safety codes as well as the National Electrical Code NEC the National Fire Protection Agency NFPA where applicable Follow the Canadian Electrical Code CEC in Canada...

Страница 2: ...preconditioned air is typically mixed with return air going back to the air handler for final conditioning Table of Contents General Safety Information 1 Unit Overview 2 Receiving Handling Storage 3 D...

Страница 3: ...nt condensation Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose t...

Страница 4: ...cessary If the unit is to be mounted on its side Reference the Mounting Options sections of this IOM then service clearance should be on the electrical input side Access Panel Locations Outdoor and ex...

Страница 5: ...plugs in the holes where the bolts were removed from in Step 6 Step 8 Position the blowers to line up with the desired discharge location The motor needs to be on the discharge end of the blower and...

Страница 6: ...ed Hanging Vibration Isolator Assembly Side Discharge End IMPORTANT The ERC M unit can be hung in any orientation The installation contractor is responsible for safely mounting the unit to provide app...

Страница 7: ...Wheel Dia 1 Fan Wheel Dia n n R o tation R o tation Length of Straight Duct GOOD POOR GOOD POOR GOOD POOR Turning Vanes SYSTEM EFFECT FACTOR CURVES FPM X 100 OUTLET VELOCITY 0 5 10 15 20 25 30 35 40 4...

Страница 8: ...tion and frosting on the energy recovery core Frost Control is a selectable timer control that will prevent frosting Frost control uses a Therm O Disc P N 314886 T O D 60T11 L15 10F mounted in the out...

Страница 9: ...9 Energy Core Ventilator Mounting Wiring HOA Controller Mounting HOA Wiring ERV Control PCB GPN 387192...

Страница 10: ...nts are swapped slide SW1 switch on ERV PCB A and B motors to reverse Agency Approval UL E479135 Conditions of Acceptability 1 ERV Controller must be mounted in a suitable end use enclosure 2 Load mot...

Страница 11: ...ate 0 10V Motor command Voltage at Motor Motor command voltage must be than 2 00V Validate Frost control is not activated Check SW1 Inlet Outlet switch B Motor does not turn ON No contact closure betw...

Страница 12: ...No ___________________________________ Unit Serial No _____________________________________ Start Up Date ____________________________________ Start Up Personnel Name __________________________ Start...

Страница 13: ...ower to the ERC M prior to inspection or servicing Failure to comply with this safety precaution could result in serious injury or death Improper installation adjustment alteration service or maintena...

Страница 14: ...order to maintain optimum sensible and latent energy transfer In reasonably clean environments such as schools offices or retail stores the energy recovery core should be inspected annually and cleane...

Страница 15: ...motor will still not rotate the motor will not attempt to start again until power is cycled Thermal Protection The motors will have an internal thermal protection which electronically regulates the R...

Страница 16: ...ngs Tighten collars and fasteners Wheel out of balance Clean replace or rebalance Low airflow cfm Fan speed too low Increase fan speed Dirty filters or energy core Replace filters and or follow the cl...

Страница 17: ...____________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ________________________...

Страница 18: ...____________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ________________________...

Страница 19: ...____________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ________________________...

Страница 20: ...and connection questions see the schematics that shipped with your unit They can typically be found attached to the main control panel door Mechanical and Controls Manuals Find current mechanical and...

Отзывы: