CHIMNEY INSTALLATION 

1.  Assemble the first chimney section with the adaptor (provided by the chimney manufacturer) using three 

¾” (19 mm) screws. 

2.  Screw this assembly to the fireplace using four ¾” (19 mm) screws.  

3.  Continue the installation following the instructions in the chimney manufacturer’s manual. (Figures #6 

through #14) 

4.  To avoid overheating the walls of the enclosure, a minimum 2” (51 mm) clearance must be provided 

between the chimney and any combustible materials.  

5.  The chimney must rise at least 3’ (914 mm) over its juncture with the roof and exceed by at least 

2’ (610 mm) any wall, roof or building located within a radius of 10’ (3 m). Any length of chimney 
exceeding the roof by 5’ (1.5 m) or more, must be braced using tie rods or guy wires. (Figure #6.1) 

6.  To limit creosote formation, it is strongly recommended that an empty enclosure space be left between the 

chimney stack and the outer framing of the chimney. Make sure that at all times a minimum clearance of 
2” (51 mm) separates the chimney and any combustible materials. 

NOTE:   Since May 1997, whatever the type of fireplace or building, safety standards require that the fireplace 

and the full length of an interior chimney up to the ceiling be enclosed. 

INSTALLATION INSTRUCTIONS FOR MASONRY APPLICATION  

WARNING:  Before starting installation, the masonry chimney must be inspected by a qualified sweep. 

The following requirements must be respected: 

1.  The chimney must be absolutely clear of any soot residue or creosote. Check for cracks, loose or missing 

bricks that could inhibit correct installation of the liner. 

2.  The clearance to combustible must be a minimum of 1” between the outside of the masonry and any wood 

framing or loose insulation. 

3.  The chimney must be built in accordance with the current building code. 

4.  No other appliance can be connected to the same chimney. 

5.  The connector parts are not necessary if the connection between the insulated length and the stainless steel 

liner is done within the masonry chimney. 

Содержание Saguency FP8

Страница 1: ...PREFABRICATED WOOD BURNING FIREPLACE INSTALLATION AND OPERATION MANUAL Keep this manual for future reference Standards ULC S610 UL 127 EPA Phase II Revised June 2009 Web Wite valcourtinc com...

Страница 2: ...u will need to show evidence of the date you purchased your unit Keep your sales invoice We also recommended that you register your warranty online at www valcourtinc com Registering your warranty onl...

Страница 3: ...lace Finish 17 USE AND SAFETY 21 Creosote 22 Chimney Fire Safety Procedures 22 Feeding and Controlling Combustion 22 MAINTENANCE 25 Glass and Metal Plating 25 Replacing Refractory Bricks 25 Door Insta...

Страница 4: ...y is the BTU indicated on the EPA label smaller than the one advertised You will notice a difference between the BTU output as indicated on the unit s white EPA label affixed to the glass and the BTU...

Страница 5: ...kirk Super Vent JSC 1 Solid Pack 6 Selkirk Hart Cooley TLC 1 Solid Pack 6 Selkirk Sure Temp ST 1 Solid Pack 6 Selkirk CF Sentinel CF 2 Solid Pack 6 Selkirk Super Pro 2100 ALT 2 Solid Pack 6 Selkirk Su...

Страница 6: ...install the fireplace where it will not be necessary to cut any floor or ceiling joists Figure 2 The fireplace must be installed against a finished wall Do not install the fireplace against a moisture...

Страница 7: ...7 Figure 2 Various Fireplace Locations Figure 3 Chimney Configurations...

Страница 8: ...of elbows Chimney Number of Elbows Minimum Height Straight installation 15 4 6 m 1 15 offset 2 15 elbows 15 4 6 m 2 15 offsets 4 15 elbows 18 5 5 m 1 30 offset 2 30 elbows 15 4 6 m 2 30 offsets 4 30 e...

Страница 9: ...Install a flexible air duct that is 4 102 mm in diameter and a maximum length of 20 6 1 m If a longer duct is required increase diameter to 6 but the maximum length will then be 40 12 2 m The outside...

Страница 10: ...stall the fan on the pegs at the back of the fireplace behind the lower louver 12 3 Connect the terminals onto the thermo disc found under the fireplace floor 12 4 Insert a 110 volt wire into the box...

Страница 11: ...11 Figure 5 Hearth Extension Installation...

Страница 12: ...12 DOOR OVERLAY INSTALLATION Your Valcourt fireplace is equipped with a door overlay See drawing below for installation details...

Страница 13: ...ming of the chimney Make sure that at all times a minimum clearance of 2 51 mm separates the chimney and any combustible materials NOTE Since May 1997 whatever the type of fireplace or building safety...

Страница 14: ...Slip through the hole a 45 or 30 liner elbow and connect it to the liner 6 Add a small liner section to the liner elbow which will allow the liner to extend at least 12 measured at the top of the lin...

Страница 15: ...15 Figure 6 Masonry chimney installation Figure 6 1 Minimum Chimney Height...

Страница 16: ...16 Figure 7 Straight Chimney Installation Figure 8 Chimney with Elbows Installation Figure 9 Exterior Chimney Installation Figure 10 Isolated Chase Chimney Installation...

Страница 17: ...the enclosure a minimum 2 51 mm clearance must be provided between the chimney and any combustible materials Never fill the enclosure space with insulation or any combustible material If the fireplace...

Страница 18: ...18 Figure 11 Fireplace Finishing Figure 12 Mantel Positioning...

Страница 19: ...19 Figure 13 Installation of Combustible and Non Combustible Materials...

Страница 20: ...20 Figure 14 Chimney Enclosure...

Страница 21: ...us It is not cause for concern 8 During the first fire you may detect a certain odor and the coating and oil protecting certain appliance parts may smoke a little If you open a window these will quick...

Страница 22: ...er to do so open the air control to its maximum for approximately 15 seconds prior to opening the fireplace door Then proceed by opening the door very slowly Open it by 2 to 4 52 to 104 mm for 10 seco...

Страница 23: ...the air intake damper depends on a number of factors including the flue s configuration and the percentage of humidity in the wood Three average sized logs on a bed of embers should take 3 to 4 hours...

Страница 24: ...ze of the flue and the air intake duct is adequate the flue and air duct are not obstructed and the air supply is sufficient to sustain combustion Low heat production It is possible the fireplace door...

Страница 25: ...wool or oven cleaner as they will scratch the glass Only wash when the stove is cold Use a glass cleaner and a soft cloth to polish the plated finish on the door frame Do not use abrasives such as ste...

Страница 26: ...ideal position has been achieved lock the pintles in place by tightening the pintle screws Adjust the pressure on the gasket using the centre adjustment screw located at the right of the combustion c...

Страница 27: ...wetter the wood the less heat it generates and the more creosote it produces If the wood being burned is very wet inspect the chimney every month it is used 7 Make sure the chimney is reasonably clean...

Страница 28: ...DISTRIBUTION KIT The Gravity Distribution Kit may be used to heat rooms located above behind and either side of the room where the fireplace is located Note that if the hot air outlets are located at...

Страница 29: ...The Forced Air Distribution Kit can be used to heat adjacent rooms or lower floors located up to 50 15 2 m from your Valcourt Fireplace Only 6 15 cm flexible isolated duct can be use for this install...

Страница 30: ...h a back draft damper Figure 19 Both alternatives require electrical power Make sure all electrical connections are made in the correct order and comply with local regulations as well as the applicabl...

Страница 31: ...d must not exceed the wholesale price of the replacement part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide...