15
B. Frame the fireplace with vertical studs on each side of the fireplace running from floor to
ceiling (see Figure 15). Position the studs back from the front edge of the fireplace,
leaving a space the thickness of the facing material so that the facing can be installed flush
with the fireplace facing (within limitations of Figure 15). Frame headers between the
vertical studs only as follows:
Place 2 x 3 or 2 x 4 headers, only along the upper part of the front, side and back
faces. Do not put wood or any combustible material within the area above the fireplace
except on the front facing.
Place headers only as required to support the facing and mantel.
WARNING: DO NOT PACK REQUIRED AIR SPACES WITH INSULATION OR
OTHER MATERIAL.
WARNING: THE FIREPLACE MUST NOT BE IN CONTACT WITH ANY
INSULATION OR LOOSE FILLING MATERIAL. COVER THE
INSULATION WITH DRYWALL PANELS AROUND THE
FIREPLACE.
Figure 12