Frequently Asked Questions

How do I know if the clock is receiving data?

Perform Diagnostic 2. See the section labeled “Diagnostic Test #2 - Comprehensive Test”. The result should 
correspond to your system’s synchronization settings. 

Example 1: The two-wire digital system should result in the clock recieving communication within the  
last hour. 

Example 2: Once-a-day sync systems may return a result of 11 hours or more, depending on when you 
conduct the test. In this case, the test should be conducted less than nine hours after the synchronization 
signal is sent.

What size utility/gang box is needed?

A standard single gang box is required for wall mounting a clock. However, if you are installing a double 
mount or flag-mount clock, then a standard double gang box is required.

Do I need to power up all the clocks at the same time?

No. Clocks that are added to the system after power up will begin running and wait for correction signals 
from the master clock. Sync-wire systems may take up to 24 hours to receive a correction signal.

Do I have to reset the clock if it suffers a power outage?

No. The clock will resume operation after the power outage, and will adjust to the correct time as soon as 
it receives a signal from the master clock.

What happens if I power the Valcom Wired Clock before connecting the master clock?

The clock will begin to run, but the time displayed will be incorrect. As soon as signal wires from the 
master clock are connected and a synchronization signal is sent, the Valcom Wired Clock will correct itself 
to display the correct time.

Can I manually set the time on the clock?

No. Furthermore, attempting to open the front crystal or moving the hands manually will damage the clock 
and void your warranty.

Содержание V-A2412

Страница 1: ...d Roanoke VA 24019 USA P 540 563 2000 F 540 362 9800 www valcom com Valcom Wired Analog Clocks Installation Manual V2 0 Current as of November 2016 V A2412 V A2412B and V A2416 V A2416B V A11012 V A11...

Страница 2: ...Installation 9 15 Double Mount Installation 16 20 Wiring Information 2 Wire Digital Communication 21 3 Wire Synchronous Sync Wire Communication 24V 22 3 Wire Synchronous Sync Wire Communication 110VA...

Страница 3: ...power circuit for the clock must be attached to a circuit breaker that can be reset by the user PHYSICAL INJURY HAZARD If you are standing on an object while installing your clock make sure that the o...

Страница 4: ...P 540 563 2000 F 540 362 9800 www valcom com Identify Your Clock A label containing the part number of your clock is attached to the clock movement ORIGINAL CLOCKS V A2412 V A2416 V A11012 V A11016 B...

Страница 5: ...32x1 2 screw M4 0 5x10 10x1 5 Self tapping screw Wall anchor Additional grounding wire with connector 1 2 2 1 1 1 PLEASE NOTE A user will also have to provide a Phillips head screwdriver a small slot...

Страница 6: ...floor CHECK YOUR WIRING The voltage between the white and black wires should measure 105 126 volts AC in the 110 volt model or 21 5 26 5 21 5 26 5 volts DC in the 24 volt model If you are using the 24...

Страница 7: ...ed 7 Remove the gearbox pin then if the case is made of metal attach the grounding wire to the grounding tab below and to the right of the clock movement 6 Insert the wall anchor into the hole then re...

Страница 8: ...mounting bracket The screws should pass through the top and bottom holes on the clock followed by the top and bottom holes of the mounting bracket 9 Attach the clock to the mounting piece so that the...

Страница 9: ...Wall anchor Additional grounding wire with connector 1 2 not used 2 not used 1 not used 1 not used 1 Description Valcom analog clock Mounting Bracket Quantity 1 1 not used Picture Flag Mount Installat...

Страница 10: ...E A user will also have to provide a Phillips head screwdriver a small slot head screwdriver a drill with a 1 4 inch drill bit a pencil a double gang box Four wall anchors that can support 50 lbs and...

Страница 11: ...um 4 Attach the mounting plate to the gang box using only two of the four long silver 6 32x1 screws With the mounting plate as a guide use the pencil to trace the locations of the four larger holes at...

Страница 12: ...any wiring through the mounting plate and attach a grounding wire to the mounting plate using one of the larger centered holes and the 10 32x3 8 screw 6 Reattach the mounting plate this time using all...

Страница 13: ...plate so that the lip is on the top of the base and the holes for the screws are on the bottom of the base Hang the base on the mounting plate attach the wires from the bottom of the pole to the wire...

Страница 14: ...nal details depending on your system 2 Wire Digital 3 Wire Sync Yellow Black White Black White Yellow 27 24 26 23 To next clock Power Common Master Clock CLOCK 1 Gang Box Green Green Ground 13 Remove...

Страница 15: ...otation that you wish it to be viewed You should hear a snapping noise as the four clips on the adapter secure the clock in place Insert the screws again to complete the installation 16 If you feel th...

Страница 16: ...analog clock Mounting Bracket Quantity 2 2 not used Picture Included in Package Included in Double Mount Kit Included in Wiring Kit A PK 12 2A PLEASE NOTE A user will also have to provide a Phillips...

Страница 17: ...communication wiring to the gang box See the sections of this manual labeled Wiring Information for additional details depending on your system If you are using a 2 wire system pull the YELLOW and GRE...

Страница 18: ...ate and attach a grounding wire to the mounting plate using one of the larger centered holes and the 10 32x3 8 screw 6 Reattach the mounting plate this time using all four long silver 8 screws then in...

Страница 19: ...ng the two black screws you set aside before 10 Attach the power connectors to the wires you threaded through the pole Consult the diagrams below for additional help or see the sections of this manual...

Страница 20: ...uld hear a snapping noise as the four clips on the adapter secure the clock in place Insert the screws again to complete the installation 12 Attach a power connector to the ports on the bottom of each...

Страница 21: ...A2412B or V A2416B Wiring Information 2 Wire Digital Communication Valcom Master Clock V D2425B or V D2440B V C6124P and the V CCU are ordered as a V VCU Data In 2 Wire Digital Output to Clocks 24 VDC...

Страница 22: ...ice charge will cover minor repairs major repairs will be subject to additional charges for parts and labor This Limited Warranty is in lieu of and excludes all other warranties expressed or implied a...

Страница 23: ...k Circuit 10 Amp Contact Rating or Black Power Green Ground White Neutral Yellow Reset 24VDC or Clock Circuit 1 Clock Circuit 2 27 26 25 24 23 22 27 26 25 24 23 22 or means one pair of ports or the ot...

Страница 24: ...rcuit 10 Amp Contact Rating or Black Power Green Ground White Neutral Yellow Reset 110VAC or Clock Circuit 1 Clock Circuit 2 27 26 25 24 23 22 27 26 25 24 23 22 or means one pair of ports or the other...

Страница 25: ...g mount clock then a standard double gang box is required Do I need to power up all the clocks at the same time No Clocks that are added to the system after power up will begin running and wait for co...

Страница 26: ...ired Clock will automatically recognize the protocol being used as soon as it receives data Can I change protocols if the system is running Yes There are two ways of doing this 1 Do nothing Within thr...

Страница 27: ...sive Test 2 Compare the time that the last signal was recieved to the parameters of your protocol If the amount of time since the last signal was recieved is more than the amount of time since the clo...

Страница 28: ...Test 1 Protocol Verification Original Only The purpose of Diagnostic 1 is to tell the user which protocol the master clock is using to communicate with the secondary clock Diagnostic 1 may be enabled...

Страница 29: ...c Test 1 Protocol Verification B Model Only The second hand will remain on this number for 3 minutes and then the clock will revert to displaying the accurate time If the LED is flashing red A compreh...

Страница 30: ...ay how much time has passed since the clock last received a communication signal Diagnostic Test 2 Comprehensive Test Original Only The clock hands will remain on these numbers for three minutes and t...

Страница 31: ...ours ago Clock received communication between 8 and 9 hours ago Clock received communication between 9 and 10 hours ago Clock received communication between 10 and 11 hours ago Clock received communic...

Страница 32: ...nufacturer s default Diagnostic 3 may be enabled by holding down the diagnostic button for five seconds If the Valcom Wired clock is performing this diagnostic then a green LED on the back will flash...

Страница 33: ...l of the clock hands are pointing to 12 the test was completed successfully At the end of Diagnostic three the clock hands will be set to 12 00 00 The clock will not resume normal operation until the...

Отзывы: