Section 3 - Installation
MC036 - Low Level Detection Alarm/AutoRefill Systems
After the control box and the probe have been installed, an initial system test
should be conducted. To test the system, follow these steps:
1.
Pressurize system.
2.
Inspect for leakage around fittings.
3.
Disconnect probe from probe cable.
4.
Plug main line cord into main power supply.
5.
Turn the control switch to the “ON” position.
The flashing light should flash on and
off. The audio alarm should also sound
if the “PROBE IN” connector was wired
for a dual sensor.
6.
Connect the probe to the probe cable.
Warning devices should turn off.
Testing the LLD
Alarm System
Internal Connections
Item
Description
Part Number
41 Wire
terminal
075xx244
43 Cable
assy.
030xx425
57
Beacon, red, low profile
105xx036
Figure 3-7. Wiring Diagram for Internal Connections (LLD Alarm System)
Please see the Parts List Section for more information.