11. Light according to instructions on the heater or within
owner’s manual.
12. It is extremely important to use the proper size and
type of gas supply line to assure proper functioning of
the heater. Contact your fuel gas supplier for proper
line sizing and installation.
13. This heater can be configured for use with either L.P.
vapor withdrawal or natural gas. Consult the
dataplate, located on the blower outlet side of the
case assembly, for the gas configuration of the
specific heater. Do not use the heater in an L.P. gas
liquid withdrawal system or application. If you are in
doubt, contact PSI.
14. Eventually, like all electrical/mechanical devices, the
thermostat can fail. Thermostat failure may result in
either an underheating or overheating condition which
may damage critical products and/or cause animal
injury or death. Critical products and/or animals
should be protected by a separate back-up control
system that limits high and low temperatures and also
activates appropriate alarms.
15. Take time to understand how to operate and main-
tain the heater by using this Owner’s Manual. Make
sure you know how to shut off the gas supply to the
building and also to the individual heater. Contact
your fuel gas supplier if you have any questions.
16. Any defects found in performing any of the service or
maintenance procedures must be eliminated and
defective parts replaced immediately. The heater
must be retested by properly qualified service
personnel before placing the heater back into use.
17. Do not exceed the input rating stamped on the
dataplate of the heater. Do not exceed the burner
manifold pressure stated on the dataplate. Do not
use an orifice size different than specified for the
specific input rating of this heater, fuel type
configuration and altitude.
8
1. Ventilation must be provided as indicated in the
Heater Specification table of this manual or on the
data plate of the heater.
2. Ventilation Requirements:
a. Canadian Installations, Agricultural Confinement
Building Heater, Gas-Fired Brooder.
-- A ventilation system shall be provided in
accordance with national, provincial, local
codes of CAN/CGA-B149 if local code
requirements do not exist.
-- CAN/CGA-B149 requires the building have
ventilation of not less than 3 cfm per 1,000
BTUH input of the heater. Ventilation must be
provided as indicated in the Heater
Specification table of this manual or on the
data plate of the heater.
b. Canadian Installations, Agricultural Building
Heater.
-- A ventilation system shall be provided in
accordance with national, provincial, local
codes or CAN/CGA-B149 if local code
requirements do not exist.
-- Installation requires the building have
ventilation of not less than 3 cfm per 1,000
BTUH input of the heater. Ventilation must be
provided as indicated in the Heater
Specification table of this manual or on the
data plate of the heater.
-- Mechanical ventilation shall be interlocked with
the heater to prevent heater operation unless
the ventilation air flow is proven by an air flow
proving device.
-- Air for combustion shall be supplied from
outdoors. The size of the opening shall be in
accordance with Table 5.2.2A of CAN/CGA-
B149.
-- The opening (or duct termination if ducted)
shall be within 1 foot (300 mm) above, and
within 2 feet (600 mm) horizontally from the
burner level of the heater.
-- An opening to the outdoors shall be located in
accordance with local code requirements, or
CAN/CGA-B149 if local code requirements do
not exist.
VENTILATION
(Optional accessory.)
(Appearance of the outlet on heater may vary from model to model.)
1. Optional air diverters can be installed in the heater
outlet to provide two 45 degree paths to the heated
air as it exits the heater. Installation options incude
installing the diverters in such a way as to broadly
distribute the air in two 45 degree paths or to focus
the air flow in one 45 degree direction.
a. 40,000, 6
60,000, aand 2
225,000 B
BTUH H
Heaters
Mount the air diverter to the outlet duct of the
heater by lining up the screw holes in the diverter
with the holes in the duct. Secure in place with
the screws included with the air diverter.
b. 150,000 B
BTUH H
Heaters
Insert the tabs of air diverters between sheet
metal case front and blower outlet. Loosen the
blower outlet screws if necessary.
(Continued oon ppage 9
9)
AIR DIVERTER
INSTALLATION INSTRUCTIONS