5. Configure the analog output channel settings:
a. In
Parameter
, select the probe and the measurement parameter that controls the
output channel. The unit of the parameter is set automatically.
b. In
Scale low end
and
Scale high end
, define the lower and upper ends of the
measurement scale for the chosen output parameter.
c. In
Error output
, define the output level indicating that the device is in error state.
d. In
Low clipping limit
, define the point (in mA below the output range) when the
output is clipped due to being out of range.
e. In
High clipping limit
, define the point (in mA or V above the output range) when the
output is clipped due to being out of range.
6. If the output channel is off, in the
General
tab, set the output channel on.
7. Repeat
for all the analog output channels you want to use.
To see the changes you made, select
. Then use the left and right arrows at the
bottom of the touchscreen to navigate to the
I/O status
view.
More information
‣
Testing analog outputs on touchscreen (page 78)
Chapter 6 – Configuring transmitter using touchscreen display
77