A.3.2 Status registers
Table 16 Modbus status registers (read-only)
Register
number
Address
Register description
Data
format
Notes
513
0200
hex
Device status
16-bit
integer
0000
hex
: Status OK; if other values
are returned, see
in
Solving typical problems (page 39)
.
514
0201
hex
Error code
32-bit
integer
Used by Vaisala Technical Support
when solving device problems
519
0206
hex
Temperature
measurement status
16-bit
integer
0000
hex
: Status OK
0004
hex
: Under range
0008
hex
: Over range
0080
hex
: Sensor failure
0100
hex
: Measurement not ready
520
0207
hex
CO
2
measurement
status
1)
Device internal temperature measurement. Measurement accuracy not specified.
2) Applicable to CO
2
measurement only.
A.3.3 Test value registers
Read the known test values from the test registers to verify the functionality of your Modbus
implementation.
Table 17 Modbus test registers (read-only)
Register
number
Register
address
Register description
Data
format
Test value
7937
1F00
hex
Signed integer test
16-bit
integer
-12345
7938
1F01
hex
Floating point test
32-bit
float
-123.45
7940
1F03
hex
Text string test
text
Text string: "-123.45"
Appendix A – Modbus reference
51