User's Guide ______________________________________________________________________
130 _________________________________________________________________ M211296EN-A
Local Serial Line
Observation and alarm messages can be sent over local RS232 and
RS485 lines. The following line parameters are fixed in AWS for both
COM0 (RS232) and Data Out (RS485):
Table 30
Serial Line Parameters
Parameter Value
Speed 9600
bps
Data bits
8
Stop bits
1
Parity None
Use the following parameters to control which messages are sent to local
serial lines (see Table 24 on page 119 and Table 25 on page 121):
- csv_to_com0
- csv_to_local
- table_to_com0
- table_to_local
- sms_to_com0
- sms_to_local
- alrmet_to_local
- alrmet_to_com0
- alrtech_to_local
- alrtech_to_com0
Set interval of the selected observation message type by (see Table 23 on
page 118):
- csv_interval
- sms_interval
- table_interval