- 12 -

0020140122_02 - 05/13

INSTALLATION

EN

4.2.2 

Wall-mounting of the product

The control unit is designed to be attached to a wall near the main 

tank inside a dwelling.

3

3

4

1

1

2

2

235

Key

1 Screws

2   Attachment holes

3 Holes

4 Plugs

 

Determine the position depending on the requirements of the 

preceding chapter: “Appliance location”.

4.3 Electrical 

Installation

e

 Danger! 

Incorrect installation can cause electric shock or 

appliance damage.

The electrical connection of the appliance must be 

made only by a qualified engineer.

• 

Ensure system is electrically isolated. 

Protect the electrical installation by following the 

guidance indicated in the “Technical data” 

chapter.

e

 Danger! 

• 

The length of the power supply cable must not 

exceed 10 metres.

 

The electrical installation in the dwelling must permit the 

power supply to the equipment to be isolated by a double pole 

isolation switch and be fused. The double pole isolation switch 

must incorporate a gap of 3mm between the contacts.

 

Use a power cable suitable for the main connection, minimum 

1.5 mm. If the cable is damaged, it must be replaced by a 

quali

fi

 ed engineer.

The external wiring must be earthed, with correct polarity and in 

accordance with current standards.

The manufacturer declines any responsibility for damages to 

persons or others caused by the incorrect installation of the 

appliance earthing. This includes failure to comply with current 

standards.

 Caution!

These pipes can become very hot which will damage 

the cables or the system.

• 

The electrical cables must not be attached to or in 

contact with the hydraulic pipes. 

4.3.1 

Description of connections

All of the internal connections are made directly to the circuit 

board.

2

3

1

Key

1 Cable 

clamp

2 Divisible wire grommet

3  Separating high and low voltage

The circuit board connectors are divided into two parts. The left 

part accepts a 230V power supply whereas the right part is used 

for 24V power.

230V connectors (High voltage) 

230V~

CYL.

2

1

DHW 

CH1

CH2

ON

DHW 

OFF

1

2

-

+

BUS

NTC

230V~

CYL.

2

1

DHW 

CH1

CH2

ON

DHW 

OFF

1

2

3

4

5

Key

1  230V supply connector (3 pins: earth / neutral / live)

2  Cylinder thermostat connector (2 pins)

3  Heating zone 1 valve (3 pins: earth/neutral/ live)

4  DHW valve ON (3 pins: earth / neutral / live)

5  DHW valve OFF - Heating zone 2 valve (3 pins: earth/neutral/ live) 

Содержание VR 66

Страница 1: ...Installation instructions GB IE VR 66 Control Centre VR 66 Installation instructions For the competent person ...

Страница 2: ......

Страница 3: ...g and installation 11 4 1 Preparing the mounting and installation 11 4 2 Mounting the product 11 4 3 Electrical Installation 12 5 Commissioning 13 5 1 Filling 13 5 2 Venting 13 5 3 Switching on 13 5 4 Multizone specific adjustment 13 5 5 Restart and check 13 6 User information 14 7 Maintenance 14 7 1 Trouble shooting 14 7 2 Main supply cable 14 8 Decommissioning 15 9 Recycling and disposal 15 9 1 ...

Страница 4: ...ance with BS EN 7671 2 1 General safety advices Before to read this chapter also read the general safety advice of the operating instructions 2 1 1 Danger to life by electric shock Touching live connections can cause serious personal injury Before carrying out any work on the product switch off the power supply Secure the power supply against being switched on again 2 1 2 Danger to life by escaping...

Страница 5: ...ll be necessary to install the unit in a location where it will not be exposed to moisture or water splashes Observe the electrical protection EP contained in the technical data Any other use than the use described in the instructions at hand or any use extending the described use is not intended Any direct commercial or industrial use is also deemed to be improper 2 3 Rules and regulations 2 3 1 ...

Страница 6: ...sed to demonstrate compliance with Building Regulations and should be provided to the customer for future reference Installers are required to carry out installation commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme Visit www centralheating co uk for more information...

Страница 7: ...r with the initial start up of the boiler i If a VR65 is replaced by a VR66 it has to be set on monozone mode 3 2 2 Priorities in boilers are defined as follows Display Meaning 0 Hot water priority The 3 port valve is in the heating or hot water position depending on the operating mode With 2 port valves either the DHW valve or the CH valve is open both valves are closed on standby 1 Enable mid po...

Страница 8: ...ic hot water cylinder 8 NTC not supplied 9 Cylinder thermostat 10 Heating circuit 11 Overheating safety if underfloor heating A Boiler circuit return B Boiler circuit flow C Cold water supply D Domestic hot water outlet DHW cylinder with NTC DHW cylinder with thermostat 3 port valve electrical connections Connect the live wire white or brown of the valve to the L of the CH1 connector Connect the e...

Страница 9: ...6 2 8 3 A B 9 10 4 12 7 5 1 C D 1m min 10 10 1 2 6 4 3 6 Key 1 Room thermostat 2 System boiler 3 DHW valve 2 port valve 4 Heating 2 port valve 5 Electrical supply 6 VR66 control unit 7 Bypass necessary with open vent boilers 8 Domestic hot water cylinder 9 NTC not supplied 10 Cylinder thermostat 11 Heating circuit 12 Overheating safety if underfloor heating A Boiler circuit return B Boiler circuit...

Страница 10: ... can store different target temperatures for heating and hot water modes i The multizone mode is only compatible with VRT350 No other room thermostats are compatible The multizone mode will NOT support weather compensation and cannot be used on Y plan systems with three port motorised valves The standard installation for multizone mode is characterised by 1 or 2 port valves for zoning 1 or 2 VRT350...

Страница 11: ... Open vent or system boiler 3 VRT350 room thermostat zone 2 4 Connection block not supplied 5 NTC not supplied 6 Heating zone 2 2 port valve 7 DHW valve 2 port valve 8 Heating zone 1 2 port valve 9 Electrical supply 10 VR66 control unit 11 Bypass necessary with open vent boilers 12 Domestic hot water cylinder 13 Cylinder thermostat 14 Overheating safety if underfloor heating as far as possible or ...

Страница 12: ...6 1 2 3 7 4 1 C Key 1 VRT350 thermostat zone 1 2 Combi boiler 3 VRT350 thermostat zone 2 4 Connection block not supplied 5 Heating zone 2 2 port valve 6 Heating zone 1 2 port valve 7 Electrical supply 8 VR66 control unit 9 Heating circuit zone 1 10 Heating circuit zone 2 11 Overheating safety if underfloor heating A Boiler circuit return B Boiler circuit flow C Cold water supply D Domestic hot wat...

Страница 13: ... Before choosing a site for the appliance carefully read the safety warnings and instructions in the user guide and installation manual Explain these requirements to the appliance user Take all necessary precautions Install the system in a room protected from frost in a convenient location accessible for wiring and servicing Do not install the control unit close to heat sources such as radiators c...

Страница 14: ...m If the cable is damaged it must be replaced by a qualified engineer The external wiring must be earthed with correct polarity and in accordance with current standards The manufacturer declines any responsibility for damages to persons or others caused by the incorrect installation of the appliance earthing This includes failure to comply with current standards b Caution These pipes can become ve...

Страница 15: ...tructions of its installation manual Refer to the installer manual 5 2 2 Heating circuit adjustement Venting of the heating circuit enables the purging of any air in the heating circuit valves still manually opened Open the different heating circuit air vent b Caution When venting is complete close the different heating circuit air vent and valves 5 3 Switching on Turn on all the appliances that ma...

Страница 16: ... connected correctly Check the domestic fuse for the 230 V supply and re connect the power supply Replace the main supply fuse in the control unit see technical data Red LED flashes quickly 2 Hz 2 flashes second Short circuit of the connected temperature sensor NTC in the cylinder Check the cable of the temperature sensor NTC for damage Replace the temperature sensor NTC in the cylinder Red LED fl...

Страница 17: ...i By adhering to this directive you are helping the envi ronment and contributing to the preservation of natu ral resources and the protection of human health 10 Guarantee and customer service 10 1 Vaillant warranty We only grant a Vaillant manufacturers warranty if a suitably qualified engineer has installed the system in accordance with Vaillant instructions The system owner will be granted a wa...

Страница 18: ......

Страница 19: ......

Страница 20: ...Manufacturer Supplier Subject to engineering changes 0020140122_02 05 13 ...

Отзывы: