Instructions on commissioning, maintenance, and troubleshooting for auroSTOR 0020111119_02
27
6.2.4 Venting the solar circuit
a
Danger!
Risk of burns and scalds resulting from
escaping hot steam!
Hot steam can discharge from automatic
air vents which are not shut off if the sys-
tem is
in stagnation.
>
Use automatic air vents with a
manufacturer's release to at least 150 ºC.
>
Shut off the automatic air vents when
operating the system.
b
Caution!
Malfunction due to air vents that are not
shut off!
Vapourous solar fluid can escape from
automatic air vents which are not shut off
whilst the system is in stagnation. The loss
of solar fluid results in functional problems.
>
Close all automatic air vents once ven-
ting is complete.
b
Caution!
Malfunction due to unsuitable air vents!
Unsuitable air vents can be destroyed in
solar mode.
>
Only use Vaillant automatic air vents
with
a manufacturer's release to at least
150 ºC.
Solar circuit filling with
Venting via
Vent opening
for flat collectors
or
Automatic air vent
with stop cock
Automatic
air separator system
Hand pump
Absolutely vital
Alternative
Recommended
Motorised filling pump
(maximum flow rate of
< 10 l/min)
Motorised filling pump
(maximum flow rate of
> 10 l/min)
Not necessary
Recommended
Tab. 6.3 Selection of venting method in accordance
with filling type
Installation 6