Start-up 6
0020221300_04 uniSTOR HP Installation and maintenance instructions
13
5.3.7
Connecting the control
Condition
: eBUS
The thermal cut-out for the primary circuit is not used when
connecting an eBUS unit.
Condition
: 230 V control
If you use a 230 V control from a third-party manufacturer,
connect the thermal cut-out
(2)
and
(3)
for the primary circuit
to the motorised valve to isolate the heat source in the event
of a fault in the motorised valve.
5.3.8
Electric connection for the primary circuit
1.
Connect the thermostat for the primary circuit and the
thermal cut-out.
–
Diameter of the cable: 1.5 mm
²
Condition
: S plan
70
60 50
40
70
60 50
40
1
3
2
4
1
3
2
4
L
N
2
1
3
2
2
4
4
1
8
L
8L
8L
SL
▶
Connect the assembly.
Condition
: Y plan
70
60 50
40
70
60 50
40
1
3
2
4
1
3
2
4
L
N
2
1
3
2
2
4
4
1
8
L
8L
8L
SL
1
▶
Connect the plug
(1)
to the electronics box.
5.3.9
Establishing the electrical connection for the
motorised valve
▶
Establish the electrical connection for the motorised
valve.
6
Start-up
6.1
Setting the immersion heater thermostat
70
60 50
40
70
60 50
40
1
3
2
4
1
3
2
4
1
The domestic hot water temperature is controlled via the
immersion heater thermostat
(1)
.