FAULT FINDING
Does flame indicator glow and
flames increase in size to full gas
rate after approx. 2 mins?
Ye
s
Does bur
ner flame modulate/ go
out when radiator temperature
control is tur
ned left to the
horizontal position at flow
temperature of approx. 50 C?
Ye
s
Does heating flow pipe
temperature rise?
Go to sheet G
Ye
s
Check operation of bur
ner and modulation
Ensure flow and retur
n ser
vice
valves are open
No
No
No
Replace electronic board
No
Check operation of boiler in DHW
mode, does flame increase in size
to full rate? (TURBOmax Plus only)
Ye
s
Check par
tial load
setting
No
Check diagnostic code D.22
(see page 53) equals 1
(TURBOmax Plus only)
No
Go to sheet G
Ye
s
Check connections and
modulator
, replace gas valve if
bur
ner still fails to increase to full
rate
Tu
rn
main ON/OFF control to
the "0" position (TURBOmax
Plus only)
Ye
s
Inser
t a small screwdriver
through the hole in the front of
the diver
ter valve and hold
blade lightly against spindle
Tu
rn
"ON" the main ON/OFF
control
Does spindle move?
Ye
s
Replace electronic board
Replace diver
ter valve
No
Sheet F