Manual - Solar hot water systems 0020009607_02

38

a

 Danger!

Risk of bursts for the solar cylinder due to 
overpressure!
The outlet of the expansion relief valve may not 
be covered or closed.

•  Test the expansion relief valve (Fig. 5.16, pos. 

2

regularly to avoid calcification.

•  Connect the solar cylinder to the cold water supply 

(Fig. 5.16, pos. 

B

).

To ensure an optimum performance of the solar cylinder, 
in particular in installations in which the pressure-
controlled cold water outlet (Fig. 5.16, pos. 

5

) is used, 

copper pipes with a diameter of at least 22 mm should 
be used for the pipe from the main stop valve of the 
building to the solar cylinder.

 

Install the drain valve in the cold water supply at the

 

lowest point between the solar cylinder and the water 
control pack (see Fig. 5.9).

•  Install the assembled water control pack in the cold 

water supply at an appropriate place next to the solar 
cylinder.Make sure there is sufficient space for 
maintenance and the connection of the discharge pipe 
from the expansion relief valve.

If the discharge pipes are all together, the expansion 
relief valve may not be installed more than 500 mm 
away from the temperature and pressure relief valve 
(see 

2

 and 

8

, Fig. 5.1).

Caution!
Risk of bursts for the solar cylinder!
No stop valve may be installed between the cold
water control pack and the cylinder.

The Vaillant solar cylinder is supplied with an external 
hot water expansion vessel (DW EV).
Connect this expansion vessel to the installed water 
control pack as follows:
•  Screw the expansion vessel directly onto the water 

control pack (Fig. 5.16, pos. 

4

) via the connection 

intended for this purpose or

•  Connect the expansion vessel to the water control 

pack with a copper pipe or an appropriate hose. Make 
sure the expansion vessel is supported sufficiently.

Use the supplied mounting bracket if the expansion 
vessel is to be mounted on the wall.
•  Establish (if necessary) the connection to the 

pressure-controlled cold water connection of the water 
control pack (see 

5

,

 

Fig. 5.16).

h

 Note!

In areas with high water pressure (4 bar or 
more), a bath or shower mixer valve can also be 
connected to the pressure-controlled cold water 
connection (4, Fig. 5.16) of the water control 
pack to ensure the pressure of the hot and cold 
water supply to the mixer valve is about the 
same. The cold water supply for all other 
connections should be installed in front of the 
water control pack in the cold water supply to 
the solar cylinder by means of a T-piece.

5.6.3 Drain 

valve

The drain valve supplied with the auroSTOR must be 
installed as low as possible in the cold water supply 
between the solar cylinder and the water control pack 
(see Fig. 5.1).
We recommend applying a hose which reaches about 1 m 
under the base of the cylinder to the outlet of the drain 
valve.

Pipe for the outlet of the expansion relief valve

•  Connect the temperature and pressure relief valve and 

the expansion relief valve to the tundish with a 15 mm 
pipe and lay the discharge pipe from the tundish as 
described in Section 5.7.1, Discharge pipework.

5.7 Discharge 

pipework

5.7.1 Discharge 

pipework

The outlet connections of both the temperature and 
pressure relief valve and expansion relief valve should 
be connected in 15 mm copper tube to the tundish 
supplied. The tundish should be installed vertically, as 
close to the uniSTOR as possible and within 500 mm of 
the temperature and pressure relief outlet. It must be 
positioned away from any electrical components and 
installed in the same space as the uniSTOR cylinder, so 
that it is visible to the user. The D1 discharge pipe from 
the T&P Valve/Expansion valve can be teed together 
upstream of the tundish (see fig. 5.1).
The discharge pipework must be installed using 
minimum 22 mm copper pipework from the 22 mm 
connection on the tundish to a safe and visible discharge 
point.
There must be a vertical section of pipe at least 300 mm 
long, below the tundish before any bends or elbows in 
the pipework. Increase the diameter of the pipework if 
the total resistance of the discharge pipework exceeds 
the figures shown in the table below. The installation of 
the discharge pipework must be in accordance with G3 
(refer to Section 2.2, Regulations in Great Britain).

5 Installation

Содержание Solar System and auroSTOR unvented solar...

Страница 1: ...For the installer owner Start up maintenance and troubleshooting manual notes for the operator Solar System and auroSTOR unvented solar cylinder Solar hot water systems GB...

Страница 2: ...the solar circuit pipes 35 5 3 4 Connection of the collectors to the solar pump unit 35 5 3 5 Bleeding of the solar circuit 36 5 4 Installation of the reheating circuit piping 36 5 5 Installation of t...

Страница 3: ...R solar cylinder The symbols used in the manual are explained below d Danger Immediate risk of serious injury or death e Danger Danger of death from electric shock e Danger Risk of burns or scalding a...

Страница 4: ...national regulations and must be in stalled to suit site conditions Observe all national regulations including Working at Heights Regulations 2005 Health and Safety at Work Act 1974 Electricity at Wor...

Страница 5: ...collector covered d Danger Risk of being burned or scalded by hot solar fluid or components Fill and flush the solar system when the collectors are cold Cover the collectors while doing so Danger Risk...

Страница 6: ...rating and installation instructions as well as all other applica ble documents and also compliance with the inspection and maintenance requirements a Caution Improper use of any kind is prohibited Yo...

Страница 7: ...torised 2 port valve supplied together with the solar cylinder 4 Immersion heater 5 230 V motorised 2 port valve 6 auroTHERM collector 7 Solar pump unit 8 Protection vessel 9 Solar expansion vessel 10...

Страница 8: ...third of the cylinder can be controlled by the VRS 560 or by a separate hot water programmer d Danger Risk of being scalded by hot water to provide effective protection against scalding install a ther...

Страница 9: ...usive VTK 570 sho wing direction of flow Key 1 Thermal insulation 2 Receiving tank 3 Supply or return connection 4 Temperature sensor pocket 5 Vacuum tubes 6 Thermal baffle plate 7 CPC mirror 8 U tube...

Страница 10: ...orption 95 1 0 Solar sensor sleeve mm 6 CE label 0036 Shutdown temperature according to prEN 12975 2 c 1 m s in the glass tube C 250 Shutdown temperature according to prEN 12975 2 c 1 m s at the colle...

Страница 11: ...K Efficiency Fig 4 4 Efficiency of auroTHERM collector with radiation ener gy content of 800 W m2 Pressure loss mbar Flow rate l min VTK 1140 VTK 570 0 0 20 40 60 80 100 120 0 25 0 5 0 75 1 1 25 1 5...

Страница 12: ...off line between the expansion relief valve and collection tank The size of the solar expansion vessel is based on the collector volume and the expansion volume of the solar system The expansion vess...

Страница 13: ...the pump is interrupted at cylinder temperatures higher than 90 C 4 5 Flow rate meter 0 5 1 2 3 0 5 1 2 3 4 5 6 4 5 6 L min L min 1 1 l min 1 2 Fig 4 11 Flow rate meter 0 6 l min The flow rate meter...

Страница 14: ...at exchanger reheating circuit 3 7 VIH S GB 250 S heat exchanger reheating circuit 3 7 VIH S GB 300 S heat exchanger reheating circuit 3 7 Solar pump unit 0 9 auroTHERM exclusive VTK 570 0 8 auroTHERM...

Страница 15: ...he fire conditions Polluted fire water must be disposed of according to local official regulations 6 Measures to be taken if substances are released accidentally 6 1 Individual related measures No par...

Страница 16: ...ividual components 12 3 Persistence and biodegradability information on elimination OECD 301 A test method new version Analysis method DOC acceptance Degree of elimination 70 28 d Assessment easily bi...

Страница 17: ...perature differences not absolute temperature values are important for the operation of solar systems That is why solar systems are controlled by what is referred to as temperature difference controll...

Страница 18: ...central heating override and the time control function of an additional circulation pump For wiring refer to Section 5 8 Electrical installation and the operating and installation manual of the VRT 36...

Страница 19: ...VFK fixing sets auroSTOR solar cylinders VIH S GB 200 S VIH S GB 250 S VIH S GB 300 S Item no 307206 307207 307208 Safety group with tundish 1 1 1 Motorised 2 port valve for regulation of reheating c...

Страница 20: ...Sp 2 temperature sensor immersion pocket 12 Adjustable feet 13 Return solar circuit 14 Supply solar circuit 15 Return gas fired wall hung boiler 16 Supply gas fired wall hung boiler 17 Immersion heat...

Страница 21: ...maximum solar gains from your system If other controls are utilised then the VRS 560 2 can be employed as a solar only controller and wired to work with your chosen hot water control The temperature s...

Страница 22: ...relief valve C bar 95 7 0 Net weight kg 39 44 49 Weight full kg 245 310 340 Height mm 1499 1789 2109 Cylinder connections Cold water supply 22 mm pressure pipe Hot water connection 22 mm pressure pipe...

Страница 23: ...try to system Flow out litres min of the system 10 10 0 Fig 5 5 auroSTOR hot water flow rates at 60 C Static operating pressure of the cold water supply The displayed flow rates apply to installations...

Страница 24: ...failure of the domestic water thermostat 5 1 6 Safety instructions and regulations This product has been checked for adherence to the building regulations for unvented hot water cylinder systems It m...

Страница 25: ...5 1 9 Transport A cylinder carrier handle is supplied to make the transport to the installation site easier 1 Fig 5 7 Fastening the cylinder carrier handle Fasten the carrier handle 1 to the hot water...

Страница 26: ...mperature and pressure relief valve 3 Immersion heater 4 Solar circuit flow Cylinder type A B C d A F g h R VIH S GB 200 S 1468 1499 454 384 314 589 1118 813 953 VIH S GB 250 S 1758 1789 454 384 314 5...

Страница 27: ...3 230 V motorised 2 port valve supplied with the solar cylinder 4 Immersion heater 5 230 V motorised 2 port valve 6 auroTHERM collector 7 Solar pump unit 8 Protection vessel 9 Solar expansion vessel 1...

Страница 28: ...lation of a motorised 2 port valve in the pipes of the solar system is not allowed since the safety devices in the solar circuit could be overridden by it 5 3 2 Material a Caution Risk of damage becau...

Страница 29: ...ers may be necessary for relatively large distances between the boiler and the cylinder Since all wall mounted Vaillant boilers except ecoMAX pro with open ventilation have an installed circulating pu...

Страница 30: ...xed with 10 l min cold water of 10 C if the measured static cold mains water pressure is 2 bar and the available flow rate 30 l min The solar cylinder operates satisfactorily at a mains water pressure...

Страница 31: ...te In areas with high water pressure 4 bar or more a bath or shower mixer valve can also be connected to the pressure controlled cold water connection 4 Fig 5 16 of the water control pack to ensure th...

Страница 32: ...risk of anyone coming in contact with hot water A suitable point is for example under a fixed grating above the trap of a trapped gully Low discharge pipes for example up to 100 mm above external surf...

Страница 33: ...arth the solar cylinder for potential equalisation 5 8 1 Immersion heater The auroSTOR VIH S GB 200 300 S solar cylinders have been equipped with an immersion heater by the manufacturer 1 2 4 5 3 230...

Страница 34: ...rsion heater You can find a wiring sheme on the inside of the cylinder cover 5 8 3 Combination options of the control components Boiler used eBUS capable boiler such as the Vaillant ecoTEC or a boiler...

Страница 35: ...mum temperature if you use one of the wiring schemes 2 or 4 1 2 3 N L 1 7 2 10 3 To wiring box 1 2 3 1 Fig 5 21 Electrical connection of the cylinder thermostat Wiring of the control components Wiring...

Страница 36: ...n the immersion sleeve for the bottom cylinder area Connect this temperature sensor to terminal SP 2 in the auroMATIC 560 solar control Attach the temperature sensor for the gain 2 to the return pipe...

Страница 37: ...s of an additionally protected terminal strip Establish the connections to the mains supply h Note Programme the hot water channel of the Vaillant eBUS controller to constant Program me the auroMATIC...

Страница 38: ...th Blue Brown Grey Orange Earth Blue Brown Grey Orange Hot Water 2 Port Valve VR 65 DHW add terminal strip LEG BYP Central Heating 2 Port Valve VR 65 CH auroSTOR cylinder 3 amp fused supply Boiler ter...

Страница 39: ...o terminal SP 2 in the auroMATIC 560 solar control Attach the temperature sensor for the gain 2 to the return pipe of the solar circuit nearby the solar cylinder Connect this temperature sensor to the...

Страница 40: ...2 Port Valve Central Heating Programmer 230 V 230 V 230 V LP UV 1 LEG BYP VRS 560 solar control 230 V EP Coll NTC auroSTOR additional terminal strip auroSTOR cylinder TCO collector pump additional ter...

Страница 41: ...in the auroMATIC 560 solar control Push a VR 10 temperature sensor 3 in the immersion sleeve for the bottom cylinder area Connect this temperature sensor to terminal SP 2 in the auroMATIC 560 solar co...

Страница 42: ...rogrammer to provide hot water when required by the cus tomer Consider carefully when the solar system might be running and try to time to HW pro grammer to run when there is unlikely to be any solar...

Страница 43: ...ctor Pump Hot Water 2 Port Valve 3 amp fused supply 230 V any Vaillant boiler Central Heating 2 Port Valve Central Heating Programmer 230 V TCO collector pump VRS 560 solar control TCO and cyl thermos...

Страница 44: ...Connect this temperature sensor to terminal SP 2 in the auroMATIC 560 solar control Attach the temperature sensor for the gain 2 to the return pipe of the solar circuit nearby the solar cylinder Conn...

Страница 45: ...mmer Boiler Terminal Strip 230 V LP UV 1 additional terminal strip LEG BYP not used to 10 way wiring box NOT separate fused spur Central Heating 2 Port Valve 230 V Hot Water 2 Port Valve auroSTOR cyli...

Страница 46: ...nal SP 1 in the auroMATIC 560 solar control Push a VR 10 temperature sensor 3 in the immersion sleeve for the bottom cylinder area Connect this temperature sensor to terminal SP 2 in the auroMATIC 560...

Страница 47: ...programmer to provide hot water when required by the cus tomer Consider carefully when the solar system might be running and try to time to HW pro grammer to run when there is unlikely to be any solar...

Страница 48: ...grammer Heating Pump if not in boiler 230 V Collector Pump additional terminal strip LEG BYP TCO collector pump EP additional terminal strip auroSTOR cylinder Coll NTC auroSTOR TCO and cyl thermostat...

Страница 49: ...when using the Vaillant filling pump It is not permitted to use manual pumps for filling Expansion vessel admission pressure During the start up the gas side admission pressure pv of the expansion ve...

Страница 50: ...d on the display 2 Table 6 1 and 6 2 provide reference values for possible pump speeds depending on the collector connection and pipe length and cross section If you use auroMATIC 560 solar control th...

Страница 51: ...programming the flow rate on the solar control refer to Section 6 1 Setting system parameters of the auroMATIC 560 operating and installation manual 6 4 Filling the hot water secondary circuit a Cauti...

Страница 52: ...cylinder 2 Fig 6 4 and immersion heater 1 Fig 6 4 to the middle position about 45 C for start up and to achieve maximum energy efficiency Start up the boiler refer to Section 6 7 until the solar cyli...

Страница 53: ...owner that the immersion heater is intended as standby device for water heating and should not be used simultaneously with the boiler to heat up the water in the solar cylinder Tell the owner that the...

Страница 54: ...Annually Secondary return reheating Check the circulation pump Annually Check the timer time programme settings Annually Reheating does it deliver the desired deactivation temperature Annually Solar...

Страница 55: ...o max speed or unblock the rotor insert a screwdriver in the notch and turn it by hand 5 Pump dirty Dismantle the pump and clean it Close the flow rate meter and pump ball valve 6 Pump defective Repla...

Страница 56: ...imiting valve and replace it if necessary Pressure limiting valve defective Replace the pressure limiting valve Blockage in the system Unblock the blockage and replace any blocked parts Check the syst...

Страница 57: ...ing up Dirt on the valve seat of the expansion relief valve Check the expansion relief valve and reset it manually Pressure limiting valve defective Switch off the boiler and immersion heater and chec...

Страница 58: ...ating system How to control the solar system is described in the manuals for each controller h Note In the event of leaks in the water pipework close the cold water stop valve at the cylinder immediat...

Страница 59: ...You can clean the exterior of the solar cylinder with a damp cloth and a little soap a Caution Risk of damage Do not use any abrasives or solvents since they could damage the exterior or the connectio...

Страница 60: ...set properly on the controller approx 60 C recommended Check the hot water thermostat mixer setting approx 60 C recommended If the settings are correct the cylinder maybe calcified In this case notif...

Страница 61: ...ts Stuffing boxes at stop valve and fill vent valve checked for leaks retighten union nuts if necessary Temperature and pressure relief valve checked Stop valve for reheating source installed normally...

Страница 62: ...ce designation Serial number Boiler system type Open Closed Installation location of pressure limiting valve System values Hot water temperature at the nearest tap C Achievable maximum cylinder temper...

Страница 63: ...P1 min see installation manual of solar control C Switch on temperature difference Kelvin Switch off temperature difference Kelvin Other settings Important activated functions Name of the installer in...

Страница 64: ...71 Manual Solar hot water systems 0020009607_02 Start up protocol 11...

Страница 65: ...Manual Solar hot water systems 0020009607_02 72 11 Start up protocol...

Страница 66: ......

Страница 67: ......

Страница 68: ......

Страница 69: ...0020009607_02 GB 072008...

Отзывы: