Product description 2
0020288192_00
sensoHOME
Operating and installation instructions
11
MENU
→
SETTINGS
→
Installer level
→
Installation configuration
→
Active
Adjusting the flow temperature based on the cur-
rent room temperature.
→
Expan-
ded
Adjusting the flow temperature based on the cur-
rent room temperature. The system control also ac-
tivates/deactivates the zone.
–
The zone is deactivated: Current room temper-
ature + 2/16 K > set room temperature
–
Zone is activated: Current room temperature <
set room temperature - 3/16 K
The installed temperature sensor measures the current room temperature. The system con-
trol calculates a new target room temperature that is used to adjust the flow temperature.
–
Difference = Set target room temperature - current room temperature
–
New target room temperature = Set target room tempe difference
Prerequisite: In the
Zone assignment:
function, the system control and/or the remote control
is assigned to the zone in which the system control or remote control is installed.
The
Room temp. mod.:
function is ineffective if
No assignmt
is activated in the
Zone as-
signment:
function.
→
Control type:
2-point
Corresponds to an on/off control system
Analog.
Corresponds to a modulating control system
→
Zone
→
Zone activated:
Deactivate zones that are not required. All existing zones appear
in the display.
→
Zone assignment:
Assign the system control and/or remote control to the selected
zone. The system control and/or remote control must be installed
in the selected zone. The control system also uses the room
temperature sensor for the assigned unit. The remote control
uses all of the values for the assigned zone. If no zone has been
assigned to the system control and/or the remote control, the
Room temp. mod.:
function is ineffective.
→
Zone valve status:
→
Domestic hot water
→
Cylinder:
If there is an existing domestic hot water cylinder, the
Active
setting must be selected.
→
Target flow temperature: °C
→
Circulation pump:
→
Anti-legio. day:
Define the days on which you want the anti-legionella function to
run. On these days, the water temperature is increased to above
60 °C. The circulation pump is activated. The function ends after
120 minutes at the latest.
If the
Absence
function is activated, the anti-legionella function is
not carried out. As soon as the
Absence
function ends, the anti-
legionella function is carried out.
→
Anti-legio. time:
Define the time at which you want the anti-legionella function to
run.
→
Cylinder charging
hysteresis: K
The cylinder charging starts as soon as cylinder temperature <
desired temperature - hysteresis value.
Содержание sensoHOME VRT 380
Страница 17: ... Electrical installation set up 3 0020288192_00 sensoHOME Operating and installation instructions 15 A B 3 ...
Страница 40: ...3 Instalación eléctrica montaje 38 Manual de uso e instalación sensoHOME 0020288192_00 A B 3 ...
Страница 62: ...3 Instalação elétrica montagem 60 Instruções de uso e instalação sensoHOME 0020288192_00 A B 3 ...
Страница 84: ...3 Električna napeljava montaža 82 Navodila za uporabo in namestitev sensoHOME 0020288192_00 A B 3 ...
Страница 94: ...92 Country specifics VRT 380 0020288192_00 ...
Страница 95: ...0020288192_00 VRT 380 Country specifics 93 ...