29
Operating Manual geoTHERM VWS/VWW 0020051547_02
GB
Description
Unit
VWS 61/2
VWS 81/2
VWS 101/2
VWS 141/2
VWS 171/2
Internal sound level
dbA
46
48
50
52
53
Conforms to safety regulations
-
CE mark
Low Voltage Directive 73/23/EWG
EMC Directive 89/336/EWG
EN 60335
ISO 5149
Table 7.1 Technical Data VWS (ctnd.)
a
Caution!
Risk of damage!
R 407 C is a chlorine-free coolant which
does not affect the ozone layer.
Nevertheless, have any servicing work
on the coolant circuit carried out only by
accredited specialists.
7.2 Technical
Data
VWW
Description
Unit
VWW 61/2
VWW 81/2
VWW 101/2
VWW 141/2
VWW 171/2
Article number
-
0010002789
0010002790
0010002791
0010002792
0010002793
Height without connections
Width
Depth without pillars
Depth with pillars
mm
mm
mm
mm
1200
600
650
840
Weight
- with packaging
- without packaging
- ready for operation
kg
kg
kg
154
139
145
161
146
153
164
149
157
182
174
186
189
174
186
Rated voltage
- Heating circuit/Compressor
- Control circuit
- Auxiliary heating
-
3/N/PE 400 V 50 Hz
1/N/PE 230 V 50 Hz
3/N/PE 400 V 50 Hz
Fuse, slow-blow
A
3 x 16
3 x 16
3 x 16
3 x 25
3 x 25
Start-up current
- without start-up current limiter
- with start-up current limiter
A
A
26
< 16
40
< 16
46
< 16
64
< 25
74
< 25
Electrical power consumption
- min. with W10W35
- max. with W20W60
- Auxiliary heating
kW
kW
kW
1.5
3.1
6
2.1
3.8
6
2.5
4.9
6
3.5
6.8
6
4.3
7.7
6
EN 60529 level of protection
-
IP 20
Hydraulic connection
- Heating flow and return
- Heat source flow and return
mm
mm
G 1 1/4", diameter 28
G 1 1/4", diameter 28
Heat source circuit
- max. operating pressure
- min. inlet temperature
- max. inlet temperature
MPa (bar)
°C
°C
0.3 (3)
4
20
- Nominal flow rate dT 3K
- Residual head dT 3K
- Nominal flow rate dT 4K
- Residual head dT 4K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
1816
-
1362
-
-
2604
-
1953
-
-
3045
-
2284
-
-
4267
-
3200
-
-
4983
-
3737
-
-
CH circuit
- max. operating pressure
- min. flow temperature
- max. flow temperature
MPa (bar)
°C
°C
0.3 (3)
25
62
- Nominal flow rate dT 5K
- Residual head dT 5K
- Nominal flow rate dT 10K
- Residual head dT 10K
- Electrical power consumption - pump
l/h
mbar
l/h
mbar
W
1404
297
728
450
93
1998
180
993
418
93
2371
97
1229
382
93
3370
92
1724
469
132
4173
0
2050
516
205
Table 7.2 Technical Data VWW
Appendix 7
Содержание geoTHERM VWS 61/2
Страница 1: ...geoTHERM ES GB...
Страница 2: ......
Страница 3: ...Para el usuario Instrucciones de uso geoTHERM VWS VWW Bomba de calor ES...
Страница 35: ...For the operator Operating Manual geoTHERM VWS VWW Heat pump GB...
Страница 66: ......
Страница 67: ......
Страница 68: ...0020051547_02 ESGB 072008...