9 Start-up
28
Installation and maintenance instructions flexoTHERM exclusive 0020196687_03
9.3
Running the installation assistants
The installation assistant is launched when the heat pump is
switched on for the first time.
Menu
→
Installer level Configuration
▶
Press
to confirm that you wish to start the installation
assistant.
◁
All heating, cooling and domestic hot water demands
are blocked whilst the installation assistant is active.
Note
You cannot exit the installation assistant until
the environment circuit type has been set.
▶
To access the next point, confirm by pressing
in each
case.
9.3.1
Setting the language
▶
To confirm the set language and to avoid unintentionally
changing it, press
twice.
9.3.2
Setting the environment circuit type
The following environment circuit types can be set:
–
Ground/brine
–
Air/brine
–
Ground water/brine
9.3.3
Setting the cooling technology
You must set the installed cooling technology.
When using ground/brine as the heat source, active cooling
is limited to a brine output temperature of 40 °C in order to
protect the source/probe borehole. If this temperature is ex-
ceeded (> 40 °C), active cooling mode is switched off. This
limit can only be changed by Vaillant Customer service.
9.3.4
Enabling the electric back-up heater
On the system control, you can select whether the electric
back-up heater is to be used for heating mode, domestic
hot water mode or both modes. Set the maximum output for
the electric back-up heater at the heat pump's control panel
here.
▶
Activate the internal electric back-up heater with one of
the following output levels.
▶
Ensure that the maximum output for the electric back-up
heater does not exceed the output of the fuse protection
for the household electricity system (rated currents, see
Technical Data).
Note
Otherwise, the home's internal circuit breaker
may trigger if, when there is insufficient heat
source output, the electric back-up heater that
is not derated is switched on.
Output levels for the 400 V electric back-up heater
–
External
–
2.0 kW
–
3.5 kW
–
5.5 kW
–
7 kW
–
9 kW
9.3.5
Purging the building circuit
▶
Start the check programme
P.05
in order to purge the
building circuit. (
→
Page 33)
9.3.6
Purging the environment circuit
▶
Start the check programme
P.06
in order to purge the
environment circuit. (
→
Page 33)
Conditions
: Air/brine heat source
–
Programme duration of approx. 1 hour. In addi-
tion to purging, the programme includes a self-
test of the air/brine collector which checks the fol-
lowing points: Phase errors, communication with
outdoor unit, brine pressure, safety cut-out of the
defroster heater, brine pump operation, brine cir-
cuit flow rate, fan, sensor faults, temperature bal-
ancing, calibration of the heat pump brine sensor,
calibration of the air/brine collector brine sensor,
inversion of brine lines, brine circuit purging func-
tion
9.3.7
Telephone number for the competent
person
You can store your telephone number in the appliance
menu.
The user can display it in the information menu. The tele-
phone number can be up to 16 digits long and must not con-
tain any spaces. If the telephone number is shorter, end the
entry after the last digit by pressing
.
All of the digits to the right will be deleted.
9.3.8
Ending the installation assistant
▶
Once you have run through the installation assistant suc-
cessfully, confirm by pressing
.
◁
The installation assistant will close and will not launch
again when the product is next switched on.
9.4
Calling up the installer level
1.
Press
and
at the same time.
2.
Navigate to
Menu
→
Installer level
and confirm by
pressing
(
OK
).
3.
Set the value
17
(code) and confirm by pressing
.
9.5
Changing the set language
1.
Press and hold
and
at the same time.
2.
Also briefly press
reset
.
3.
Press and hold
and
until the display shows the
language setting option.
4.
Select the required language.
5.
Press
twice to confirm this change.
6.
To confirm the set language and to avoid unintentionally
changing it, press
twice.