Appendix
0020261389_02 ecoTEC plus Installation and maintenance instructions
61
I
Horizontal terminal positioning
Applicability:
Great Britain
OR Ireland
BS 5440-1 recommends that fanned flue chimney terminals should be positioned as follows:
a) at least 2 m from an opening in the building directly opposite, and
b) so that the products of combustion are not directed to discharge directly across a boundary if the products are likely to
cause a nuisance to a neighbour or discharge over a walkway or patio.
For IE see current issue of IS 813.
For boilers covered within this manual.
1) Dimensions D, E, F and G:
These clearances may be reduced to 25 mm without affecting the performance of the boiler. In order to ensure that the con-
densate plume does not affect adjacent surfaces the terminal should be extended as shown below.
Balcony/eaves
Gutter
Adequately secured
air/flue gas pipe
The flue pipe must
protrude beyond any overhang
2) Dimension H:
This clearance may be reduced to 25 mm without affecting the performance of the boiler. However, in order to ensure that
the condensate plume does not affect adjacent surfaces a clearance of 300 mm is preferred.
For 1 and 2 above you can use a flue gas management kit to enable the termination point to be positioned and directed away
from the building fabric.
J
Gas adjustment values
Set values, G20 natural gas
VU 446/5-5
(H-GB)
VU 606/5-5
(H-GB)
CO
₂
after 5 minutes
in full load mode with
front casing closed
Checking
during start-
up
9.2
±
1.0 vol.
%
9.2
±
1.0 vol.
%
Checking
after reset-
ting
9.2
±
0.3 vol.
%
9.2
±
0.3 vol.
%
CO
₂
after 5 minutes
in full load mode with
front casing removed
Checking
during start-
up
9.0
±
1.0 vol.
%
9.0
±
1.0 vol.
%
Checking
after reset-
ting
9.0
±
0.3 vol.
%
9.0
±
0.3 vol.
%
Set for Wobbe index W
₀
14.1 kW
⋅
h/m
³
14.1 kW
⋅
h/m
³
O
₂
after 5 minutes in
full load mode with
front casing closed
Checking
during start-
up
4.5
±
1.8 vol.
%
4.5
±
1.8 vol.
%
Checking
after reset-
ting
4.5
±
0.5 vol.
%
4.5
±
0.5 vol.
%