Appendix
0020149561_01 ecoCRAFT exclusive Installation and maintenance instructions
47
VKK GB
806/3-E R1
VKK GB
1206/3-E R1
VKK GB
1606/3-E R1
VKK GB
2006/3-E R1
VKK GB
2406/3-E R1
VKK GB
2806/3-E R1
Boiler dimension, width
695 mm
695 mm
695 mm
695 mm
695 mm
695 mm
Boiler dimension, height
1,285 mm
1,285 mm
1,285 mm
1,285 mm
1,285 mm
1,285 mm
Boiler dimension, depth
1,240 mm
1,240 mm
1,240 mm
1,550 mm
1,550 mm
1,550 mm
Approx. net weight
200 kg
220 kg
235 kg
275 kg
295 kg
310 kg
Ready for operation
weight approx.
210 kg
235 kg
255 kg
300 kg
320 kg
340 kg
Technical data
–
G20 power/loading G20
VKK GB
806/3-E R1
VKK GB
1206/3-E R1
VKK GB
1606/3-E R1
VKK GB
2006/3-E R1
VKK GB
2406/3-E R1
VKK GB
2806/3-E R1
Nominal heat output
range P at 80/60 °C
13.6
… 78.2 kW
21.3
… 113.4 kW
26.2
… 156.5 kW
43.1
… 196.8 kW
47.0
… 236.2 kW
51.0
… 275.5 kW
Nominal heat output
range P at 60/40 °C
14.1
… 80.4 kW
22.1
… 116.5 kW
27.1
… 160.8 kW
44.2
… 201.0 kW
48.2
… 241.2 kW
52.3
… 281.4 kW
Nominal heat output
range P at 50/30 °C
14.4
… 82.4 kW
22.7
… 119.4 kW
27.8
… 164.8 kW
45.3
… 206.0 kW
49.1
… 247.2 kW
53.6
… 288.4 kW
Nominal heat output
range P at 40/30 °C
14.7
… 84.1 kW
23.1
… 121.8 kW
28.4
… 168.2 kW
46.2
… 210.2 kW
50.4
… 252.2 kW
54.7
… 294.3 kW
Maximum heat input,
heating side
80.0 kW
115.9 kW
160.0 kW
200.0 kW
240.0 kW
280.0 kW
Minimum heat input
14.0 kW
22.0 kW
27.0 kW
44.0 kW
48.0 kW
52.0 kW
Technical data
–
Heating
VKK GB
806/3-E R1
VKK GB
1206/3-E R1
VKK GB
1606/3-E R1
VKK GB
2006/3-E R1
VKK GB
2406/3-E R1
VKK GB
2806/3-E R1
Max. flow temperature
adjustment range (default
setting: 80 °C)
35 … 85
℃
35 … 85
℃
35 … 85
℃
35 … 85
℃
35 … 85
℃
35 … 85
℃
Permissible total over-
pressure
0.6 MPa
(6.0 bar)
0.6 MPa
(6.0 bar)
0.6 MPa
(6.0 bar)
0.6 MPa
(6.0 bar)
0.6 MPa
(6.0 bar)
0.6 MPa
(6.0 bar)
Floor-standing boiler ca-
pacity (without connec-
tion piece)
5.74 l
8.07 l
10.4 l
12.73 l
15.05 l
17.37 l
Circulation water volume
(with reference to
Δ
T= 20 K)
3.44 m
³
/h
4.99 m
³
/h
6.88 m
³
/h
8.60 m
³
/h
10.33 m
³
/h
12.05 m
³
/h
Pressure loss (with refer-
ence to
Δ
T= 20 K)
0.008 MPa
(0.080 bar)
0.0085 MPa
(0.0850 bar)
0.009 MPa
(0.090 bar)
0.0095 MPa
(0.0950 bar)
0.01 MPa
(0.10 bar)
0.0105 MPa
(0.1050 bar)
Condensate volume at
heating mode 40/30 °C
13 l/h
20 l/h
27 l/h
34 l/h
40 l/h
47 l/h
Heating standby losses
per day (heating 70 °C)
<0.4%
<0.4%
<0.4%
<0.4%
<0.4%
<0.4%
Technical data
–
Electrics
VKK GB
806/3-E R1
VKK GB
1206/3-E R1
VKK GB
1606/3-E R1
VKK GB
2006/3-E R1
VKK GB
2406/3-E R1
VKK GB
2806/3-E R1
Rated voltage
230 V/50 Hz
230 V/50 Hz
230 V/50 Hz
230 V/50 Hz
230 V/50 Hz
Permissible connected
voltage
190 … 253 V
190 … 253 V
190 … 253 V
190 … 253 V
190 … 253 V
190 … 253 V
Built-in fuse (slow-blow,
H or D)
4 A
4 A
4 A
4 A
4 A
4 A
Max. electrical power
consumption
260 W
260 W
320 W
320 W
320 W
320 W
Standby electrical power
consumption
8 W
8 W
8 W
8 W
8 W
8 W
Level of protection
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
Unit protection class
Class I
Class I
Class I
Class I
Class I
Class I
Test symbol/registration
no.
CE-
0063BS3740
CE-
0063BS3740
CE-
0063BS3740
CE-
0063BS3740
CE-
0063BS3740
CE-
0063BS3740