Appendix
0020149561_01 ecoCRAFT exclusive Installation and maintenance instructions
33
Code Parameter
Values or explanations
Default set-
ting
Own setting
D.43
Floor-standing boiler temperature
Not
adjustable
D.44
Digitised ionisation value
Display field 0 to 1020
> 700 no flame
< 450 flame detected
< 250 very good flame
Not
adjustable
D.47
Outside temperature (with weather
compensator)
Actual value in °C, if the outside temperature sensor is
connected to X41
Not
adjustable
D.50
Offset for minimum speed
In rpm/10, adjustment range: -40 to +40
Nominal
value set in
factory
D.51
Offset for maximum speed
In rpm/10, adjustment range: -40 to +40
Nominal
value set in
factory
D.54
Switch-on hysteresis
0-10 K
−
2
D.55
Switch-off hysteresis
0 - 10 K
6
D.60
Number of temperature limiter shut-
downs
Number of shutdowns
Not
adjustable
D.61
Number of ignition device cutoffs
Number of unsuccessful ignitions in the last attempt
Not
adjustable
D.63
Number of air-monitoring switch-off
sequences
Number of shutdowns
Not
adjustable
D.64
Average ignition time
In seconds
Not
adjustable
D.65
Maximum ignition time
In seconds
Not
adjustable
D.67
Remaining burner anti-cycling time
In minutes
Not
adjustable
D.68
Unsuccessful ignitions at 1st attempt
Number of unsuccessful ignitions
Not
adjustable
D.69
Unsuccessful ignitions at 2nd at-
tempt
Number of unsuccessful ignitions
Not
adjustable
D.71
Maximum target value heating flow
temperature
40 … 85
℃
75
℃
D.72
External heating pump overrun after
cylinder charging
Adjustable from 0 to 600 seconds
300 s
D.73
Cylinder charging offset, raising the
temperature between the target cyl-
inder temperature and the target flow
temperature when cylinder charging
0 - 25 K
25 K
D.75
Max. charging time for domestic hot
water cylinder without independent
control system
20 - 90 min
45 minutes
D.76
Floor-standing boiler type
14 = ecoCRAFT
Not
adjustable
D.77
Limit on cylinder charging output in
kW
Adjustable cylinder charging output in kW
Maximum value = nominal heat output
Automatic
cylinder par-
tial load
D.78
Cylinder charging temperature limit
(target flow temperature in cylinder
charging mode) in °C
55 °C-85 °C
80
℃