Installation manual auroTHERM 0020057143_04
5.2
Weighting and arrangement of the frames
First of all, define the necessary load of the frames
based on Tab. 5.1.
Load [kg/collector]
Height above ground
Angle of attack
0-10 m
10-18 m
18-25 m
30°
159
178
197
45°
225
252
279
60°
276
309
342
Table 5.1 Flat roof installation load
a
Caution!
The roof may collapse!
Before installation, check the maximum roof
load!
If necessary, call a technician.
For the required space and the distances among frames
please see Tab. 5.2.
A
B
D
E
Number of
collectors
A*
30°
45°
60°
C
D*
A
B
F
B
F
B
F
Vertical
1**
1136
1283
2800
1740
4060
2080
4810
2357
-
-
2
2300
1150
-
3
3563
1263
4
4826
5
6089
6
7352
7
8615
8
9878
9
11141
10
12404
C
C
F
Horizontal
1
1650
883
1250
1173
2030
1387
2560
1812
-
-
2
3900
1950
-
3
5963
2063
4
8026
5
10089
6
12152
7
14215
8
16278
9
18341
10
20404
* Dimension A can vary by +/- 50 mm in connection with dimension D.
** Possible only with 4 offset gravel trays.
1)
Angle of attack (30°, 45° or 60°)
Table 5.2 Distances among frames
a
Caution!
Starting from an installation height of 25 m
above ground, a specific static calculation must
be made!
a
Caution!
For determining the installation location, keep a
distance of 1 m from the roof edge! A different
distance causes high wind loads.
Flat roof installation 5