5 Installation

8

Installation and maintenance instructions auroSTOR 0020221298_04

Caution.
Risk of material damage by drilling
through the product.

The product may be damaged by drilling
work.

Do not drill through the product.

Caution.
Risk of material damage to the cylinder.

If an unvented hot water cylinder is fitted at
a high level (eg, loft space), potential dam-
age to the cylinder may occur if the correct
method of draining is not followed.

In certain circumstances and at the dis-
cretion of the installer, install a WRAS ap-
proved automatic air vent on the hot water
outlet at the highest point.

6

7

8

11

10

12

13

1

2

4

3

5

9

14

1

Solar circuit return

2

Solar circuit flow

3

Heat generator heating
return

4

2-port motorised valve

5

Heat generator heating
flow

6

Temperature and pres-
sure expansion relief
valve

7

Secondary circuit return

8

Domestic hot water
outlet

9

Safety group

10

Expansion vessel

11

Tundish

12

Dry pocket for the solar
circuit temperature
sensor

13

Cold water inlet

14

Drain valve

5.2.1

Connecting the solar circuit

1.

Connect the solar circuit to the inlet

(1)

and the outlet

(2)

.

Installing the solar yield sensor

2.

Install the yield sensor on the solar coil outlet close to
the cylinder.

5.2.2

Connecting the product to the heating circuit

1.

Connect the heating circuit to the inlet

(5)

and the outlet

(3)

.

Minimum diameter of the copper pipe:

22 mm

Note

Ensure that the distance between the heat
generator and the product is as small as pos-
sible in order to prevent heat losses.

Installing the 2-port motorised valve

AUT

O

MAIN 

OPEN

2.

Install the 2-port motorised valve at the heating coil's
inlet or outlet.

3.

For the 2-port motorised valve, follow the installation
direction that is marked by an arrow.

4.

The 2-port motorised valve can be installed vertically or
horizontally. For horizontal installation, align the valve
head so that it is facing upwards.

5.2.3

Installing the drain valve

The drain valve must be supplied by the customer.

Install the drain valve at the height of the cold water supply
or further below this level.

5.2.4

Installing the safety group

Caution.
Excessive pressure in the domestic hot
water cylinder

Excessive pressure in the domestic hot water
cylinder may cause the cylinder to burst.

Ensure that the expansion relief valves
are not blocked.

Ensure that there is no isolation valve
between the safety group and the cylin-
der.

Содержание auroSTOR VIH S GB 200/3 BES

Страница 1: ...lation and maintenance instructions auroSTOR VIH S GB 3 BES GB IE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 492191 18 0 Fax 492191 18 2810 info vaillant de www vaill...

Страница 2: ...unit horizontally 7 5 2 Hydraulic connection 7 5 3 Electrical installation 11 6 Start up 14 6 1 Setting the immersion heater thermostat 14 6 2 Cold water inlet pressure 14 6 3 Setting the thermostati...

Страница 3: ...tenance instructions for the product and any other system com ponents installing and setting up the product in ac cordance with the product and system ap proval compliance with all inspection and main...

Страница 4: ...orrect tool 1 4 5 Risk of material damage caused by frost Do not install the product in rooms prone to frost 1 4 6 Risk of injury due to the heavy weight of the product Make sure that the product is t...

Страница 5: ...appropriate Building Regu lations The Benchmark Checklist can be used to demon strate compliance with Building Regulations and should be provided to the customer for future reference Installers are re...

Страница 6: ...tion area Select a sensible installation site and take into consideration the routing of the pipework system Install the cylinder as close as possible to the heat generator in order to minimise heat l...

Страница 7: ...and temper ature and pressure relief valve 4 5 Product dimensions 595 638 90 379 317 265 154 B A D C E F Dimensions mm VIH S GB 200 3 BES VIH S GB 250 3 BES VIH S GB 300 3 BES A 1 265 1 535 1 745 B 9...

Страница 8: ...and the outlet 2 Installing the solar yield sensor 2 Install the yield sensor on the solar coil outlet close to the cylinder 5 2 2 Connecting the product to the heating circuit 1 Connect the heating c...

Страница 9: ...tall the expansion vessel close to the product 2 Install a pipe at the expansion vessel and connect the terminal to the safety assembly 6 5 2 6 Installing a discharge pipe 600 mm 300 mm D2 2 1 D1 1 Te...

Страница 10: ...ontact with the waste water and provided that the sys tem is not visible Do not install any valves or stopcocks on the drain pipework Make sure that the discharge pipe from the tundish to the drain ha...

Страница 11: ...and N are live Switch off the power supply Secure the power supply against being switched back on Caution Risk of material damage by drilling through the product The product may be damaged by drilling...

Страница 12: ...pply 70 60 50 40 1 3 2 4 L N 1 L N 3 2 4 1 2 1 Remove the cover for the electrics on the cylinder 2 Install a separate power supply for the immersion heater in accordance with the applicable standards...

Страница 13: ...nctional module 5 3 7 Connecting the control Condition eBUS The thermal cut out for the primary circuit is not used when connecting an eBUS unit Condition 230 V control If you use a 230 V control from...

Страница 14: ...eck the immer sion heater in particular 9 Open the highest hot water supply valve and then the lowest hot water supply valve and let the water flow Water running time 5 min 10 Close all of the draw of...

Страница 15: ...draw off valve 2 Secure a hose to the drain valve 3 Position the hose at a suitable drain 4 Open the highest hot water tap in the installation 5 Open the drain valve and drain the product completely...

Страница 16: ...le 3 Reduce the temperature of the thermostat to 55 C 4 Replace the thermostat Irregular domestic hot water output at the valve 1 Defective expansion vessel 2 Thermal control 1 Set the expansion vesse...

Страница 17: ...16 0 kW 15 2 kW Flow rate 900 l h 900 l h 900 l h Pressure loss in the heat exchanger heating circuit 50 mbar 50 mbar 50 mbar Volume of the heat exchanger heating circuit 3 7 l 3 7 l 3 7 l Volume of...

Страница 18: ...z 230 240 V 50Hz 230 240 V 50Hz Thermostat 230 240 V 50Hz 230 240 V 50Hz 230 240 V 50Hz IP rating 21 21 21 Technical data Material VIH S GB 200 3 BES VIH S GB 250 3 BES VIH S GB 300 3 BES Cylinder mat...

Страница 19: ...Appendix 0020221298_04 auroSTOR Installation and maintenance instructions 19 D Commissioning Checklist...

Страница 20: ...UROV KDYH EHHQ WWHG LQ FRPSOLDQFH ZLWK 3DUW RI WKH XLOGLQJ 5HJXODWLRQV Yes Type of control system if applicable Y Plan S Plan Other Is the cylinder solar or other renewable compatible Yes No What is t...

Страница 21: ...Date Engineer name Company name Telephone No Comments Signature SERVICE 05 Date Engineer name Company name Telephone No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Comm...

Страница 22: ...n valve 8 Draining the product 15 E Electricity 3 F Filling and purging the heating circuit 14 Filling and purging the product 14 Filling and purging the solar circuit 14 Frost 4 H Handing over to the...

Страница 23: ......

Страница 24: ...byshire DE56 1JT Telephone 0330 100 3461 info vaillant co uk www vaillant co uk These instructions or parts thereof are protected by copyright and may be reproduced or distributed only with the manufa...

Отзывы: