background image

System with system control (0020232127) 4

0020243831_00 System assistant

15

Work step

Selected information/measures

10

Outdoor unit

Evacuating the refrigerant circuit

Drain the nitrogen that was poured in.

Connect a vacuum pump.

Drain the refrigerant circuit in two rounds of 30 minutes each.

After each round, check whether the pressure is stable:

0.1 kPa (1.0 mbar) absolute pressure

11

Outdoor unit

Adding additional refrigerant

Condition:

Basic length of the refrigerant pipe > 15 m

For each additional metre (above 15 m), add additional refrigerant:

30 g/m for an output of up to 5 kW

70 g/m for an output of 7 kW or higher

12

Outdoor unit

Releasing the refrigerant

Turn the isolation valves as far as they will go.

4.4

Installing the heating and domestic hot water circuit

uniTOWER installation and maintenance instructions, from section 5.1 onwards

Accessory set-up instructions

Work step

Selected information/measures

13

Indoor unit

Installing the domestic hot and cold water

connection

Installing heating circuit connections

Observe the connection symbols.

uniTOWER installation and maintenance instructions, section 3.7

14

Heating circuit

Connecting the buffer cylinder

Connecting the bypass valve

15

Heating circuit

Connecting the additional expansion vessel

Condition:

The dimension of the installed expansion vessel is not sufficient

16

DHW circuit

Connecting the expansion vessel

Ensure that there is sufficient dimensioning.

If required, adjust the pre-charge pressure.

17

DHW circuit

Connecting a circulation pump

18

Safety devices

Installing the safety devices

Ensure that all of the required safety device have been installed in the sys-

tem.

4.5

Installing the electrical connections

aroTHERM installation and maintenance instructions, from section 6.1 onwards

uniTOWER installation and maintenance instructions, from section 6.1 onwards

multiMATIC installation instructions, from section 4.1 onwards

Accessory set-up instructions

Work step

Selected information/measures

19

System control

Connecting the system control

Ideally, install the system control in a living room.

Conditions:

Installation in the indoor unit's electronics box

Install a separate humidity sensor.

20

Outdoor temperature sensor

Connecting the outdoor temperature sensor

21

Outdoor unit

Establishing the power supply

Select a correct cable cross-section.

Comply with the connection conditions for the energy supply company.

Determine whether an electrical connection 1~/230 V or 3~/400 V (

data

plate) is required.

Determine whether the power supply should be set up using a single-tariff

meter or a dual-tariff meter.

Condition:

Depending on the installation site

Install one or two type-B residual-current circuit breakers for the outdoor unit,

depending on the connection type.

Содержание aroTHERM VWL Series

Страница 1: ...rigerant split heat pump system aroTHERM VWL AS uniTOWER VWL IS AT BE de DE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info vaillan...

Страница 2: ...Telefon 04621 30 60 89 0 Mail info unidomo com ffnungszeiten Mo Fr 8 00 17 00 Uhr a member of DAIKIN group Individuelle Beratung Komplettpakete Kostenloser Versand ber 15 Jahre Erfahrung Hochwertige...

Страница 3: ...it 8 3 4 Installing the heating and domestic hot water circuit 9 3 5 Installing the electrical connections 9 3 6 Completing installation 10 3 7 Starting up the system 10 3 8 Implementing settings on t...

Страница 4: ...does not replace the instructions that are enclosed with the install ation s system components Carry out a complete and proper installa tion and start up as described in detail in the instructions for...

Страница 5: ...e described here The settings on the control for the indoor unit and or the system control refer to the basic system diagram that was shown before Configure the system in accordance with the end user...

Страница 6: ...g circuits Additional functions System control Special equipment Regu lated Non reg ulated 0020253231 aroTHERM VWL AS uniTOWER VWL IS X 1 X Buffer cylinder Outdoor temperature sensor 0020232127 aroTHE...

Страница 7: ...3 System without system control 0020253231 6 System assistant 0020243831_00 3 System without system control 0020253231 3 1 Basic system diagram...

Страница 8: ...System without system control 0020253231 3 0020243831_00 System assistant 7 Wiring diagram...

Страница 9: ...oduct Condition Optional accessory Installing the installation set hydraulics If required separate the indoor unit into two modules Remove and dispose of the carrying straps after the unit has been se...

Страница 10: ...ust the pre charge pressure 17 Safety devices Installing the safety devices Ensure that all of the required safety device have been installed in the sys tem 3 5 Installing the electrical connections a...

Страница 11: ...equirements for the heating filling and supplementary water 2 Outdoor unit Switching on the power supply 3 Indoor unit Switching on the power supply 3 8 Implementing settings on the indoor unit s cont...

Страница 12: ...er level Test menu Sensor actuator test All displayed faults have been eliminated The heating installation is adapted 14 Menu Installer level Configuration Configure the system in accordance with the...

Страница 13: ...4 System with system control 0020232127 12 System assistant 0020243831_00 4 System with system control 0020232127 4 1 Basic system diagram...

Страница 14: ...System with system control 0020232127 4 0020243831_00 System assistant 13 Wiring diagram...

Страница 15: ...duct Condition Optional accessory Installing the installation set hydraulics If required separate the indoor unit into two modules Remove and dispose of the carrying straps after the unit has been set...

Страница 16: ...dimension of the installed expansion vessel is not sufficient 16 DHW circuit Connecting the expansion vessel Ensure that there is sufficient dimensioning If required adjust the pre charge pressure 17...

Страница 17: ...he plug on the control PCB 4 6 Completing installation aroTHERM installation and maintenance instructions from section 5 5 onwards Work step Selected information measures 26 Building Sealing the wall...

Страница 18: ...ssor output control that is as efficient as possible longer cylinder charging time Normal Balanced control short cylinder charging time maximum compressor output 16 Noise reduction comp Condition Time...

Страница 19: ...29 Adaptive heat curve Condition Control installed in the living room Yes 30 Automatic cooling Condition Product with cooling mode Yes 31 Start OT cooling Condition Product with cooling mode Recommen...

Страница 20: ......

Страница 21: ...Telefon 04621 30 60 89 0 Mail info unidomo com ffnungszeiten Mo Fr 8 00 17 00 Uhr a member of DAIKIN group Individuelle Beratung Komplettpakete Kostenloser Versand ber 15 Jahre Erfahrung Hochwertige...

Страница 22: ...straat 15 B 1620 Drogenbos Tel 2 3349300 Fax 2 3349319 Kundendienst Service apr s vente Klantendienst 2 3349352 info vaillant be www vaillant be Vaillant Group International GmbH Berghauser Strasse 40...

Отзывы: