background image

1 Safety

4

Installation instructions aroTHERM 0020217827_03

Secure against being switched back on
again.

Wait for at least 3 minutes until the capa-
citors have discharged.

Check that there is no voltage.

1.3.4 Risk of death due to lack of safety

devices

The basic diagrams included in this docu-
ment do not show all safety devices required
for correct installation.

Install the necessary safety devices in the
installation.

Observe the applicable national and inter-
national laws, standards and directives.

1.3.5 Risk of being scalded by hot drinking

water

There is a risk of scalding at the hot water
draw-off points if the hot water temperatures
are greater than 50 °C. Young children and
elderly persons are particularly at risk, even
at lower temperatures.

Select the temperature so that nobody is at
risk.

1.3.6 Risk of injury or material damage due

to incorrect handling of the product

Using the fins on the front side of the product
as conductors may lead to injuries (due to
falling) or to material damage.

Do not use the fins as conductors.

1.3.7 Risk of material damage due to

additional elements in the heating
water

Unsuitable frost and corrosion protection
agents may damage seals and other com-
ponents of the heating circuit and may there-
fore also lead to leaks in the water outlet.

Only add approved frost and corrosion
protection agents to the heating water.

1.3.8 Risk of material damage caused by

using an unsuitable tool

Use the correct tool.

1.3.9 Avoid environmental damage caused

by escaping refrigerant

The heat pump contains the refrigerant
R410A. The refrigerant must not be allowed
to escape into the atmosphere. R410A is a
fluorinated greenhouse gas covered by the
Kyoto Protocol, with a GWP of 2088 (GWP
= Global Warming Potential). If this gas es-
capes into the atmosphere, its impact is 2088
times greater than the natural greenhouse
gas CO

2

.

Before the heat pump is disposed of, the re-
frigerant that is contained in it must be com-
pletely drained into a suitable vessel so that
it can then be recycled or disposed of in ac-
cordance with regulations.

Ensure that only officially certified com-
petent persons with appropriate protective
equipment carry out maintenance work on
the refrigerant circuit or access it.

Arrange for the refrigerant contained in the
product to be recycled or disposed of by
certified competent persons in accordance
with regulations.

Use only R410A as the refrigerant.

Only use a tool suitable for R410A for the
filling, pressure measurement, vacuum
generation and discharge.

Solder the lines using shielding gas. Check
the lines for leak-tightness using nitrogen.

In the event of a repair or maintenance
work, fill the refrigerant circuit with liquid
refrigerant.

If the refrigerant circuit is not leak-tight,
check which components must be repaired
or replaced.

Lower the negative pressure in the refri-
gerant circuit to max. 10 mbar (1000 Pa).

When filling the refrigerant circuit, observe
the values in the "Technical data" section.

Содержание aroTHERM VWL 55/3 A 230 V

Страница 1: ...lation instructions aroTHERM VWL 55 3 A 230 V VWL 85 3 A 230 V GB Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 492191 18 0 Fax 492191 18 2810 info vaillant de www vaill...

Страница 2: ...ing and treating the heating water filling and supplementary water 18 6 8 Filling the heating installation 19 6 9 Activating the heat pump 19 6 10 Checking the product s operation 19 6 11 Operating no...

Страница 3: ...with the product and system ap proval compliance with all inspection and main tenance conditions listed in the instruc tions Intended use also covers installation in ac cordance with the IP code Any o...

Страница 4: ...material damage caused by using an unsuitable tool Use the correct tool 1 3 9 Avoid environmental damage caused by escaping refrigerant The heat pump contains the refrigerant R410A The refrigerant mus...

Страница 5: ...deals with the collection of refrigerants system leaks particularly sys tems containing more than 3 kg of CFC or HCFC as well as the minimum level of qualification required by the technicians EC regu...

Страница 6: ...e product s operation if the measured temperature exceeds the maximum permissible temperature The maximum permissible temperature depends on the evaporation and condensation temperature The product me...

Страница 7: ...re 3 4 System diagram VWL 55 3 A 230 V e 1 3 12 16 17 19 24 15 21 14 11 4 23 20 2 22 5 13 8 9 6 7 10 A B 18 1 Fan 2 Air inlet temperature sensor 3 Ribbed pipe heat ex changer 4 Temperature sensor of t...

Страница 8: ...re in the refrigerant circuit Information on the data plate Meaning PSH min PSH max Minimum and maximum operat ing pressure in the heating circuit COP Ax Wxx Output figure coefficient of performance a...

Страница 9: ...e this may lead to malfunctions in the refrigerant circuit during subsequent operation In the worst case scenario this may lead to a fault in the whole system During transport do not tilt the heat pum...

Страница 10: ...1 2 3 Bottom view C A B B D E Product A B C D E VWL 55 3 A 230 V 740 120 490 386 70 VWL 85 3 A 230 V 778 162 550 437 102 5 1 3 Complying with minimum clearances 5 1 3 1 Installation clearance C B D A...

Страница 11: ...de the building Do not install the product Near a heat source Near flammable materials Near ventilation openings for adjacent buildings Under deciduous trees Note the following points when installing...

Страница 12: ...paths and that ice cannot build up there The condensate is discharged centrally underneath the product The condensate is heated inside the product and routed into the condensate discharge 300 B 100 38...

Страница 13: ...scope of delivery 5 2 2 Aligning the product M10 8mm 1 Align the product horizontally so that condensate can flow Note The product must be installed with the vibra tion isolating feet supplied The pro...

Страница 14: ...xible connection pipes on the product that have a length of at least 0 75 m 3 When the product is not installed at the highest point in the heating circuit install additional purging valves in places...

Страница 15: ...onnection terminals 5 4 1 Establishing the power supply The external mains connection cable must be earthed and connected with the correct polarity and in accordance with the valid regulations Check t...

Страница 16: ...due to incorrect rout ing of the supply lines If you route the supply lines for the power supply and the eBUS line through the same cable duct the signal will be disrupted Route the supply lines for t...

Страница 17: ...n use this function to call up the status code of the heat pump which provides you with information about the current operating condition of the heat pump 6 5 Calling up statistics Menu Installer leve...

Страница 18: ...ng the filling and supplementary water Before filling the installation measure the hardness of the filling and supplementary water Treating the filling and supplementary water Observe all applicable n...

Страница 19: ...re possible Open all radiator valves thermostatic valves of the heat ing installation Open the cold water tap Slowly open the filling tap Fill it with water until the required filling pressure is reac...

Страница 20: ...te Caution Risk of material damage due to frost If the minimum flow rate is too low the heat exchanger may become damaged by frost Operate the product with a sufficient flow rate see table The product...

Страница 21: ...f you require spare parts for maintenance or repair work use only Vaillant genuine spare parts 7 3 Instructions before carrying out maintenance work Observe the basic safety rules before carrying out...

Страница 22: ...3 4 5 3 6 5 1 2 1 Remove the side casing Page 13 2 Remove both screws 1 3 Lift off the cover 4 Remove both screws 2 on the right front casing 5 Remove the right front casing 6 Lift the louvred grill 3...

Страница 23: ...the following tests before introducing additional steps Make absolutely sure that the power supply was not cut and that the product is correctly connected Ensure that the service valves are open Chec...

Страница 24: ...tly Observe all relevant regulations For detailed information refer to www vaillant co uk 10 1 Arranging disposal of refrigerant Warning Risk of damage to the environment This heat pump contains the r...

Страница 25: ...X15 X13 X26 X23 X21 X22 X30 X25 X24 X25 X5 X10CA X9 X2 RL1 X3 15 16 17 12 18 19 20 21 22 23 24 25 11 9 8 7 6 5 4 3 1 2 13 14 10 1 Temperature sensor for the finned pipe heat ex changer 2 Temperature s...

Страница 26: ...15 16 17 14 12 6 1 4 5 13 19 21 24 10 25 11 20 2 3 1 Flow heating circuit temperature sensor 2 Return heating circuit temperature sensor 3 High efficiency pump with flow rate sensor 4 Expansion vesse...

Страница 27: ...13 Temperature sensor after the plate heat exchanger 14 Service valve for the high pressure range of the refrigerant circuit 15 High pressure pressure switch in the refrigerant circuit 16 High pressu...

Страница 28: ...cessary in order to prevent the remaining feed head from being exceeded Maximum value 100 mbar Max dura tion of the power inter ruption If the set value is exceeded when the power supply is dis connec...

Страница 29: ...ble range high pressure low pressure ratio too low 556 Refrigerant circuit pressure not in the permissible range condensation rate too low 557 Refrigerant circuit pressure not in the permissible range...

Страница 30: ...Product dimensions width 970 mm 1 103 mm Product dimensions height 834 mm 975 mm Product dimensions depth 408 mm 463 mm Net weight 90 kg 106 kg Hydraulic lines material Copper Copper Hydraulic connect...

Страница 31: ...ir temperature cyl inder charging 46 46 Max air flow 2 000 m h 2 700 m h Technical data Heating circuit VWL 55 3 A 230 V VWL 85 3 A 230 V Minimum operating pres sure 0 1 MPa 1 0 bar 0 1 MPa 1 0 bar Ma...

Страница 32: ...main PCB and the fan PCB is dam aged or broken F 042 Fault Coding resistor The product s coding resistor is missing or is defective Coding resistor value outside the permissible range X25 plug not co...

Страница 33: ...d area of the refrigerant circuit loss of charge Flow rate quantity too high see defined maximum flow rate Flow rate monitor defective Insufficient heat transfer in the heat exchanger F 539 Refrigeran...

Страница 34: ...e the 4 port diverter valve away from the control When moving it check that the coil voltage is correct Check the cable harness and the connections Check the temperat ure sensor for the finned tube he...

Страница 35: ...should be made aware it is ultimately their responsibility to register with the manufacturer within the allotted time period It is essential that the heat pump is serviced in line with the manufacture...

Страница 36: ...V VWHP KDV EHHQ XVKHG DQG FOHDQHG LQ DFFRUGDQFH ZLWK 6 DQG KHDW SXPS PDQXIDFWXUHU V LQVWUXFWLRQV Yes What system cleaner was used What inhibitor was used Quantity litres Is the system adequately fros...

Страница 37: ...Company name Telephone No 2SHUDWLYH 1R Comments Signature SERVICE 05 Date Engineer name Company name Telephone No 2SHUDWLYH 1R Comments Signature SERVICE 07 Date Engineer name Company name Telephone N...

Страница 38: ...E Electricity 3 F Filling 19 Front Cleaning 22 Function menu 23 G Grommet 16 H Hot water temperature 4 I Installer level 17 Intended use 3 L Live Monitor Calling up 17 M Manual Validity 6 P Product U...

Страница 39: ......

Страница 40: ...byshire DE56 1JT Telephone 0330 100 3461 info vaillant co uk www vaillant co uk These instructions or parts thereof are protected by copyright and may be reproduced or distributed only with the manufa...

Отзывы: