Appendix
32
Installation instructions aroTHERM 0020217827_03
Technical data
–
Heat pump system performance data
VWL 55/3 A
230 V
VWL 85/3 A
230 V
Heat output A-7/W35
4.42 kW
5.74 kW
A-7/W35 output figure/EN
14511 coefficient of per-
formance
2.46
2.33
Power consumption ef-
fective at A-7/W35
1.80 kW
2.46 kW
Heat output A7/W35
4.40 kW
7.07 kW
A7/W35 output figure/EN
14511 coefficient of per-
formance
4.53
4.07
Power consumption ef-
fective at A7/W35
0.97 kW
1.74 kW
Heat output A7/W45
4.09 kW
6.71 kW
A7/W45 output figure/EN
14511 coefficient of per-
formance
3.42
3.24
Power consumption ef-
fective at A7/W45
1.19 kW
2.07 kW
Heat output A7/W55
3.94 kW
6.34 kW
A7/W55 output figure/EN
14511 coefficient of per-
formance
2.73
2.66
Power consumption ef-
fective at A7/W55
1.45 kW
2.38 kW
F
Overview of fault codes
Code
Meaning
Cause
F.022
Water pressure too low
Insufficient water in the heating system
F.037
Fan fault
–
Obstruction in the product's air pipe
–
Fan motor not connected or defective
–
The connection between the main PCB and the fan PCB is dam-
aged or broken
F.042
Fault: Coding resistor
–
The product's coding resistor is missing or is defective
–
Coding resistor value outside the permissible range
–
X25
plug not connected or was connected incorrectly
F.073
Fault: Water pressure sensor
Line to water pressure sensor is broken or has a short circuit
F.086
Surface-mounted thermostat opened
–
Underfloor heating temperature too high
–
Heating circuit flow rate quantity too low
–
Underfloor heating circuit is closed
F.103
Fault: Spare part detection
–
The parameter
Max. duration power supply cut-off
has been
poorly set (see "Heat pump setting parameters" in the appendix).
–
The main PCB that is fitted as a spare part or the frequency con-
verter does not match the product.
F.514
Temp. sensor fault: Compressor inlet
Sensor is defective or incorrectly connected to the main PCB
F.517
Temp. sensor fault: Compressor outlet
F.519
Sensor fault: Return temperature
F.520
Sensor fault: Flow temperature
F.523
Sensor fault: VF1
Line to temperature sensor VF1 is broken or has a short circuit
F.526
Sensor fault: Temp. environment circuit EEV
1)
Sensor is defective or incorrectly connected to the main PCB
1) Sensor on the evaporator
2) Sensor on the condenser