8 Adapting the unit to the installation

20

Installation and maintenance instructions aroSTOR 0020290840_00

Press the rotary knob to confirm the selection.

Press the menu button to return to the original display.

8.8

Setting ventilator mode

Turn the rotary knob to set the mode

INST.MENU SET

TINGS FAN MODE

.

1 = Fan operates only when the heat pump is run-
ning. The fan speed does not automatically adjust to
the heat pump's requirements.

2 = Fan operates only when the heat pump is run-
ning. The fan runs at maximum speed.

3 = Fan operates only if the heat pump is running or if
the external control system permits this (hygrostat)

8.9

Setting the maximum heating time

1.

If you switch off this function, the domestic hot water
cylinder charging time is shortened.

INST.MENU

SET

TINGS

MAX. TIME

.

2.

Press the rotary knob.

3.

Turn the rotary knob to set the maximum heating time
via the heat pump (

Auto

/number of hours).

In

Auto

mode, the product optimises its use of

energy sources (heat pump and back-up heater) in
order to prevent the heating from starting less than
five hours after a low-tariff period has begun.

When in the

Auto

setting, the product only uses

the back-up heater during low-tariff periods and
programmed time periods. The heat pump is
used first. The back-up heater is switched on as
late as possible.

If the unit is not connected to the energy sup-
ply company's high-/low-tariff contact, it may not
recognise that the five-hour time period has star-
ted and consequently the

Auto

function may not

work.

In "Number of hours" mode, the product optimises
its use of energy sources (heat pump and back-up
heater) in order to reach the set temperature within
n hours of the heating starting.

The shorter the maximum heating time is set to,
the more often the back-up heater is switched
on and the higher the energy consumption and
consequently the energy costs as a result.

Note

The amount of power available depends
on the load relief level and the time period
(Comfort, Eco, Frost protection, High/Low
tariff) that have been programmed.

4.

Press the rotary knob to confirm the selection.

5.

Press the menu button to return to the original display.

8.10

Reading the meter status

1.

If you want to read the product's counter statuses, se-
lect this menu

INST.MENU COUN TERS

.

2.

Press the rotary knob in the

COUN TERS

menu.

No. 1 = Number of heat pump switching operations

No. 2 = Number of immersion heater switching oper-
ations

No. 3 = Function deactivated

No. 4 = Number of compressor operating hours

3.

Press the menu button to return to the original display.

8.11

Locking the control elements

1.

Turn the rotary knob until the

LOCK ING

menu is dis-

played.

If the control elements are blocked, you can only
reset the fault codes or unblock the control elements

INST.MENU LOCK ING

.

2.

Press the rotary knob to confirm.

3.

Turn the rotary knob to set the automatic level of lock-
ing.

no

= Automatic blocking is not active.

Auto

= The control elements are blocked 60

seconds after the last entry. This is how you unblock
the control elements (

Page 20).

Pro

= The control elements are blocked 300

seconds after the last entry. This is how you unblock
the control elements (

Page 20).

4.

Press the rotary knob to confirm the selection.

5.

Press the menu button to return to the original display.

8.11.1 Unblocking control elements in the Auto

mode

1.

Press and hold the menu button for three seconds.

2.

Select the rotary knob

YES

.

3.

Press the rotary knob to confirm the selection.

4.

Press the menu button to return to the original display.

8.11.2 Unblocking control elements in the Pro

mode

1.

Press and hold the menu button for three seconds.

2.

Press and hold the rotary knob and the clock button for
three seconds.

3.

Select the rotary knob

YES

.

4.

Press the rotary knob to confirm the selection.

5.

Press the menu button to return to the original display.

8.11.3 Manually locking the operator control

elements

1.

In the basic display, hold down the menu button and the
clock button for three seconds.

2.

Select the rotary knob

YES

.

3.

Press the rotary knob to confirm the selection.

4.

To lift manual locking, hold down the menu button for
three seconds .

Содержание aroSTOR VWL BM 270/5

Страница 1: ...n and maintenance instructions aroSTOR VWL BM 200 5 VWL BM 270 5 KOsq Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 492191 18 0 Fax 492191 18 2810 info vaillant de www v...

Страница 2: ...11 4 8 Removing installing the protective cover 11 5 Installation 11 5 1 Installing the air supply and air exhaust 12 5 2 Installing the water connections 14 5 3 Electrical installation 15 6 Start up...

Страница 3: ...not specified in these instructions or use beyond that specified in this document shall be considered improper use Any direct commercial or industrial use is also deemed to be improper Caution Imprope...

Страница 4: ...ny about the water hardness When deciding whether the water used must be softened follow the national regu lations standards directives and laws In the installation and maintenance instruc tions for t...

Страница 5: ...Safety 1 0020290840_00 aroSTOR Installation and maintenance instructions 5 1 16 Regulations directives laws standards Observe the national regulations stand ards directives ordinances and laws...

Страница 6: ...he operating and installation instruc tions included with the system components 2 2 Storing documents Pass these instructions and all other applicable docu ments on to the end user 2 3 Validity of the...

Страница 7: ...erature cut out 4 Immersion heater safety cut out 5 External condenser 6 Domestic hot water cylinder temperature sensor 7 Compressor 8 Pressure switch 9 Sensor head thermostatic expansion valve 10 Fan...

Страница 8: ...nsion 3 3 1 Heating mode 1 2 4 3 5 6 1 Evaporator 2 Compressor 3 Fan 4 Defrosting valve 5 Thermostatic expansion valve 6 Condenser 3 3 2 Defrosting mode 1 2 4 3 5 6 1 Evaporator 2 Compressor 3 Fan 4 D...

Страница 9: ...on site in the transport bag supplied Note The transport bag must be kept away from children in order to prevent the risk of suffoc ation 4 When transporting the product using a hand truck se cure it...

Страница 10: ...TOR VWL BM 270 5 B A B C D E F G H I Unit dimensions and connection dimensions for 200 and 270 l Page 10 Unit dimensions and connection dimensions for 200 and 270 l aroSTOR VWL BM 200 5 aroSTOR VWL BM...

Страница 11: ...t install the product near bedrooms 4 8 Removing installing the protective cover 4 8 1 Removing the covering hood x1 A B C 1 Turn the screw A on the product s ring by a few milli metres using a Torx s...

Страница 12: ...pipe Standard value L1 L2 Condition Flexible pipes 10 m Note In addition to the total length two 90 el bows can be added Condition Fixed pipes 20 m Note In addition to the total length two 90 el bows...

Страница 13: ...utside With this installation type the room is used as an energy collector The room is cooled by outdoor air which flows in via the ventilation openings Room volume at installation site 20 m Caution R...

Страница 14: ...ing Area of the installation room 20 m Minimum room height 2 20 m 5 2 Installing the water connections 5 2 1 Hydraulics installation Use flat seals Torque 20 Nm 5 2 2 Connecting the domestic hot water...

Страница 15: ...t until the condensers have discharged The product s power supply must not be interrupted by a timer 5 3 1 Carrying out the wiring 20 mm max 1 Guide the extra low and low voltage cables through differ...

Страница 16: ...Fan not running Contact closed Fan running In the menu set the Fan with external control system mode to FAN MODE 3 5 3 4 Setting the fan speed Validity aroSTOR VWL BM 200 5 OR aroSTOR VWL BM 270 5 If...

Страница 17: ...ter cylin der is full and purged before establishing the power supply Permanently connect the power supply cable to the power supply via an all pole electrical partition which can be switched off e g...

Страница 18: ...f the thermodynamic water heater and the back up heater s thermostat input Note The output alarm is not activated It is conver ted to a control output for the floor standing boiler The end user can se...

Страница 19: ...ivate the anti legionella function by setting the target temperature to a value between 60 C and maximum 70 C The automatic cycle for heating the water is activated at 22 00 If the target temperature...

Страница 20: ...ime period Comfort Eco Frost protection High Low tariff that have been programmed 4 Press the rotary knob to confirm the selection 5 Press the menu button to return to the original display 8 10 Readin...

Страница 21: ...unit along with the immersion heater 6 and its seal 10 Check the scale deposition on the immersion heater 11 Replace the seal 9 Troubleshooting 9 1 Eliminating faults Before eliminating the fault chec...

Страница 22: ...ion the product 2 Disconnect the product from the power mains 3 Close the stop cock upstream of the safety group on the cold water inlet 4 Ensure that the waste water outlet is connected to the safety...

Страница 23: ...rder to recycle the refrigerant you must collect it in a suitable vessel prior to disposing of the product 12 Customer service Validity Kosovo Vaillant P r t dh nat e kontaktit p r sh rbimin ton t kli...

Страница 24: ...lace the immersion heater 18 Record the inspection maintenance work carried out B Fault messages Overview Fault code Description Possible cause Solution Temporary operation buS PCB defective Bus conne...

Страница 25: ...C LOW PRES Low pressure inside the heat pump Air flow too low Air inlet outlet opening blocked Air pipe blocked Fan blocked or defect ive Evaporator contamin ated and blocked Evaporator frozen Air te...

Страница 26: ...issioned ERR 03 Incorrect temperature sensor readings The defrosting sensor is connected on the water connection plug The wa ter temperature sensor is connected to the air con nection plug and the air...

Страница 27: ...out of operation during high tariff 1 Only heat pump in operation during high tariff 2 Heat pump and immersion heater in operation during high tariff 1 T C MINI 43 43 43 C no no FAN MODE Current value...

Страница 28: ...12 14 18 19 16 17 10 9 15 1 1 Control panel 2 Control panel connection plug 3 Main PCB 4 Connection plug no 1 Low tariff or lower level of electrical energy generated by the photovoltaic installation...

Страница 29: ...c mixer tap 7 Circulation pump 8 Expansion relief valve 9 Expansion vessel 10 Safety assembly 11 Stopcock 12 Pressure reducer 13 Non return valve 14 Stopcock 15 Expansion vessel 16 Drain valve 17 Dome...

Страница 30: ...m Corrosion protection Maximum pressure in the drinking water circuit 0 6 MPa 6 0 bar 0 6 MPa 6 0 bar Max domestic hot water temperature with the heat pump 60 60 Max hot water temperature with the add...

Страница 31: ...the heat pump water temperat ure 55 C 700 W 700 W Nominal heat output of the heat pump water temperat ure 45 C 1 420 W 1 420 W Coefficient of performance COPDHW outdoor air temper ature 7 C extractio...

Страница 32: ...Fault messages 21 Frost 4 H Handing over to the operator 18 Heating installation leaking 4 I Immersion heater 21 Inspection work 22 24 Installation 11 Installation site 3 4 Installing the protective c...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...1 6188 671 Tel 01 6064 380 Tehni ki odjel 01 6188 673 Fax 01 6188 669 info vaillant hr www vaillant hr These instructions or parts thereof are protected by copyright and may be reproduced or distribut...

Отзывы: