Adapting the unit to the installation 8

0020290840_00 aroSTOR Installation and maintenance instructions

19

Note

When photovoltaic mode has the higher prior-
ity, domestic hot water is also heated during
periods that have not been set (e.g. holiday
mode and outside of programmed time peri-
ods).
If you only want to heat the domestic hot wa-
ter during the permitted time period, set the
priority to

no

.

Press the rotary knob to confirm the selection.

The immersion heater is supplied with electricity in
order to use the energy from the photovoltaic install-
ation.

When the fan mode is activated (

FAN MODE

), op-

tion 3 can no longer be selected.

The

SHED DING

function is not available.

Press the menu button to return to the original display.

8.4

Reading the input data

1.

If you want to read the product's input data, you must
select this menu.

DI SPLAY

INST.MENU

.

2.

Press the rotary knob in the

DI SPLAY

menu.

WATE R

= Domestic hot water temperature in the

central section of the domestic hot water cylinder

AIR INLET

= Air temperature at the air intake

T_EV APOR

= Temperature of the evaporator

If

PV MODE

is deactivated:

SHED DING

: Connection contact no. 1/low-tariff

contact input (0: Contact opened; 1: Contact
closed)

FAN CONTR.

: Connection contact no. 2/hygro-

stat input (0: Contact opened; 1: Contact closed)

If

PV MODE

is activated:

PV ECO

: Connection contact no. 1 input (0:

Contact opened; 1: Contact closed)

PV MAX

: Connection contact no. 2 input (0:

Contact opened; 1: Contact closed)

3.

Press the menu button to return to the original display.

8.5

Setting the anti-legionella function

Danger!
Risk of death from legionella.

Legionella multiply at temperatures below
60 °C.

Ensure that the end user is familiar with
all of the Anti-legionella measures in order
to comply with the applicable regulations
regarding legionella prevention.

The anti-legionella function heats the water in the product to
a temperature between 60 °C and 70 °C. The default fact-
ory setting for the target temperature is 60 °C and the anti-
legionella function is not carried out.

If the target temperature is below 60 °C, you can activate the
anti-legionella function by setting the target temperature to
a value between 60 °C and maximum 70 °C. The automatic
cycle for heating the water is activated at 22:00.

If the target temperature for the cycle is not reached within
24 hours, the cycle stops and then starts again at the next
interval deadline. If an anti-legionella cycle is interrupted by
a time period in which the back-up heater is prevented from
operating (high tariff or time programming), the anti-legion-
ella function will be restarted in the next interval deadline.

Observe the applicable regulations regarding legionella
prevention.

Turn the rotary knob to set the time interval (in days) for
the anti-legionella function.

SET TINGS

ANTI -BACT.

INST.MENU

.

Press the rotary knob.

Select the time interval between two anti-legionella func-
tion charges.

Note

The time interval can be between 0 and 99
days.

Press the rotary knob to confirm the selection.

Press the menu button to return to the original display.

8.6

Selecting the load relief stage

Condition

: Cable for low-tariff/high-tariff load relief connected

Select the components that can be used during high-
tariff periods.

Heat pump only

Heat pump and immersion heater

Turn the rotary knob to set the mode.

INST.MENU

SET TINGS

SHED DING

.

0 = No components may operate in the high-tariff
periods

1 = Only the heat pump may operate in the high-tariff
periods

2 = The heat pump and immersion heater may oper-
ate in the high-tariff periods

Note

When using a low-tariff connection,
you should not set any additional time-
programming.

Press the menu button to return to the original display.

If you are using a high-tariff connection, inform the end
user of the optimal energy use.

8.7

Setting the minimum temperature

You can use the minimum temperature function to prevent
the domestic hot water temperature falling below 38 °C. In
doing so, the back-up heater (immersion heater) supports
the heat pump until a domestic hot water temperature of
43 °C has been reached.

Depending on the parameter selection when setting the load
relief stage, the minimum temperature function may not be
available in high-tariff periods under certain circumstances.

INST.MENU

SET TINGS

T°C MINI

Press the rotary knob.

Turn the rotary knob and select a hot water temperature
of 43 °C.

Содержание aroSTOR VWL BM 270/5

Страница 1: ...n and maintenance instructions aroSTOR VWL BM 200 5 VWL BM 270 5 KOsq Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 492191 18 0 Fax 492191 18 2810 info vaillant de www v...

Страница 2: ...11 4 8 Removing installing the protective cover 11 5 Installation 11 5 1 Installing the air supply and air exhaust 12 5 2 Installing the water connections 14 5 3 Electrical installation 15 6 Start up...

Страница 3: ...not specified in these instructions or use beyond that specified in this document shall be considered improper use Any direct commercial or industrial use is also deemed to be improper Caution Imprope...

Страница 4: ...ny about the water hardness When deciding whether the water used must be softened follow the national regu lations standards directives and laws In the installation and maintenance instruc tions for t...

Страница 5: ...Safety 1 0020290840_00 aroSTOR Installation and maintenance instructions 5 1 16 Regulations directives laws standards Observe the national regulations stand ards directives ordinances and laws...

Страница 6: ...he operating and installation instruc tions included with the system components 2 2 Storing documents Pass these instructions and all other applicable docu ments on to the end user 2 3 Validity of the...

Страница 7: ...erature cut out 4 Immersion heater safety cut out 5 External condenser 6 Domestic hot water cylinder temperature sensor 7 Compressor 8 Pressure switch 9 Sensor head thermostatic expansion valve 10 Fan...

Страница 8: ...nsion 3 3 1 Heating mode 1 2 4 3 5 6 1 Evaporator 2 Compressor 3 Fan 4 Defrosting valve 5 Thermostatic expansion valve 6 Condenser 3 3 2 Defrosting mode 1 2 4 3 5 6 1 Evaporator 2 Compressor 3 Fan 4 D...

Страница 9: ...on site in the transport bag supplied Note The transport bag must be kept away from children in order to prevent the risk of suffoc ation 4 When transporting the product using a hand truck se cure it...

Страница 10: ...TOR VWL BM 270 5 B A B C D E F G H I Unit dimensions and connection dimensions for 200 and 270 l Page 10 Unit dimensions and connection dimensions for 200 and 270 l aroSTOR VWL BM 200 5 aroSTOR VWL BM...

Страница 11: ...t install the product near bedrooms 4 8 Removing installing the protective cover 4 8 1 Removing the covering hood x1 A B C 1 Turn the screw A on the product s ring by a few milli metres using a Torx s...

Страница 12: ...pipe Standard value L1 L2 Condition Flexible pipes 10 m Note In addition to the total length two 90 el bows can be added Condition Fixed pipes 20 m Note In addition to the total length two 90 el bows...

Страница 13: ...utside With this installation type the room is used as an energy collector The room is cooled by outdoor air which flows in via the ventilation openings Room volume at installation site 20 m Caution R...

Страница 14: ...ing Area of the installation room 20 m Minimum room height 2 20 m 5 2 Installing the water connections 5 2 1 Hydraulics installation Use flat seals Torque 20 Nm 5 2 2 Connecting the domestic hot water...

Страница 15: ...t until the condensers have discharged The product s power supply must not be interrupted by a timer 5 3 1 Carrying out the wiring 20 mm max 1 Guide the extra low and low voltage cables through differ...

Страница 16: ...Fan not running Contact closed Fan running In the menu set the Fan with external control system mode to FAN MODE 3 5 3 4 Setting the fan speed Validity aroSTOR VWL BM 200 5 OR aroSTOR VWL BM 270 5 If...

Страница 17: ...ter cylin der is full and purged before establishing the power supply Permanently connect the power supply cable to the power supply via an all pole electrical partition which can be switched off e g...

Страница 18: ...f the thermodynamic water heater and the back up heater s thermostat input Note The output alarm is not activated It is conver ted to a control output for the floor standing boiler The end user can se...

Страница 19: ...ivate the anti legionella function by setting the target temperature to a value between 60 C and maximum 70 C The automatic cycle for heating the water is activated at 22 00 If the target temperature...

Страница 20: ...ime period Comfort Eco Frost protection High Low tariff that have been programmed 4 Press the rotary knob to confirm the selection 5 Press the menu button to return to the original display 8 10 Readin...

Страница 21: ...unit along with the immersion heater 6 and its seal 10 Check the scale deposition on the immersion heater 11 Replace the seal 9 Troubleshooting 9 1 Eliminating faults Before eliminating the fault chec...

Страница 22: ...ion the product 2 Disconnect the product from the power mains 3 Close the stop cock upstream of the safety group on the cold water inlet 4 Ensure that the waste water outlet is connected to the safety...

Страница 23: ...rder to recycle the refrigerant you must collect it in a suitable vessel prior to disposing of the product 12 Customer service Validity Kosovo Vaillant P r t dh nat e kontaktit p r sh rbimin ton t kli...

Страница 24: ...lace the immersion heater 18 Record the inspection maintenance work carried out B Fault messages Overview Fault code Description Possible cause Solution Temporary operation buS PCB defective Bus conne...

Страница 25: ...C LOW PRES Low pressure inside the heat pump Air flow too low Air inlet outlet opening blocked Air pipe blocked Fan blocked or defect ive Evaporator contamin ated and blocked Evaporator frozen Air te...

Страница 26: ...issioned ERR 03 Incorrect temperature sensor readings The defrosting sensor is connected on the water connection plug The wa ter temperature sensor is connected to the air con nection plug and the air...

Страница 27: ...out of operation during high tariff 1 Only heat pump in operation during high tariff 2 Heat pump and immersion heater in operation during high tariff 1 T C MINI 43 43 43 C no no FAN MODE Current value...

Страница 28: ...12 14 18 19 16 17 10 9 15 1 1 Control panel 2 Control panel connection plug 3 Main PCB 4 Connection plug no 1 Low tariff or lower level of electrical energy generated by the photovoltaic installation...

Страница 29: ...c mixer tap 7 Circulation pump 8 Expansion relief valve 9 Expansion vessel 10 Safety assembly 11 Stopcock 12 Pressure reducer 13 Non return valve 14 Stopcock 15 Expansion vessel 16 Drain valve 17 Dome...

Страница 30: ...m Corrosion protection Maximum pressure in the drinking water circuit 0 6 MPa 6 0 bar 0 6 MPa 6 0 bar Max domestic hot water temperature with the heat pump 60 60 Max hot water temperature with the add...

Страница 31: ...the heat pump water temperat ure 55 C 700 W 700 W Nominal heat output of the heat pump water temperat ure 45 C 1 420 W 1 420 W Coefficient of performance COPDHW outdoor air temper ature 7 C extractio...

Страница 32: ...Fault messages 21 Frost 4 H Handing over to the operator 18 Heating installation leaking 4 I Immersion heater 21 Inspection work 22 24 Installation 11 Installation site 3 4 Installing the protective c...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...1 6188 671 Tel 01 6064 380 Tehni ki odjel 01 6188 673 Fax 01 6188 669 info vaillant hr www vaillant hr These instructions or parts thereof are protected by copyright and may be reproduced or distribut...

Отзывы: