F
ault
finding
10
Ins
tructions
for
ins
tallation
and
servicing
aquaPL
US
VUI
3
62
-7
45
Does fan run after approx. 30 secs.?
Check flue and ignition system
No
Check diagnostic code D.24
(see page 39) equal 1?
Check pitot tube (in fan outlet) and air
hoses are not obstructed and correctly
aligned.
Check or replace air pressure switch.
837/637 Check 4 pin connector for
fan speed control.
Does the fan run now?
Is 230 VAC present across fan
terminals?
Replace electronic board
Yes
No
No
Yes
No
Yes
Yes
Check/replace fan
Does the boiler
commence ignition
Check status code
(see page 38) is S.33?
Check air/flue gas system
is correctly fitted and not
obstructed
Yes
No
Replace electronic board
No
Yes
Are electrodes sparking at
the burner?
Yes
Go to sheet E
No
Check electrodes and
electrode leads.
Replace as necessary.
Sheet D
Check flue restrictor
correspond to flue length
834702_33GB_012005.qxd 09.03.2005 16:26 Uhr Seite 45