Commissioning checklist 3
0020251825_01 System installation instructions
5
Work
Comments/settings
51
Current flow temp.
Current value display
52
Heat generator 2
53
Status
Current value display (standby, heating, cooling, do-
mestic hot water)
54
Current flow temp.
Current value display
55
HEATING 1
56
Status
Current value display (off, heating mode, cooling, do-
mestic hot water)
57
Target flow temp.
Current value display
58
Max limit outs.temp.
21 °C, change in consultation with the customer, if re-
quired
59
Heating curve
0.4 to 0.6 for underfloor heating
60
Minimum temperature
15 °C
61
Maximum temperature
45 °C for underfloor heating
62
Auto Off mode
Set-back
63
Cooling possible
Yes
for underfloor heating
No
; you should not use passive cooling for compact col-
lectors and flat collectors
64
Dew point monitoring
Yes
65
Min. cool. fl. tgt temp.
18 °C
66
End OT cooling
15 °C
67
Offset dew point
2 K
68
Pump status
Current value display:
off
/
On
69
ZONE1
70
Zone activated
Current value display:
No
/
Yes
71
Day temperature
20 °C
72
Set-back temp.
15 °C
73
Room temperature
Current value display
74
Zone assignment
VRC 700
75
Zone valve status
Current value display (closed/open)
76
Domestic hot water
77
Cylinder active
Condition: Domestic hot water cylinder in the system
78
Target flow temp.
Current value display
79
Domestic hot water
60 °C
Inform the end user about the anti-legionella function
80
Current cyl. temp.
Current value display
81
Cyl. charging pump
Current value display:
off
/
On
82
Circulation pump
Current value display:
off
/
On
83
Anti-legionella day
–
Select:
off
,
Monday
,
Tuesday
,
Wednesday
,
Thursday
,
Friday
,
Saturday
,
Sunday
,
Monday -
Sunday
–
Factory setting:
off
84
Anti-legionella time
04:00
85
Cyl. boost hysteresis
5 K
86
Cylinder boost offset
25 K
87
Max. cyl. charg. time
45 min.
88
DHW req. anti-cy time
30 min.
89
Ch. pump overrun time
5 minutes
90
Parallel cyl. charging
off
91
Menu
→
Installer level
→
Service information
92
Enter contact details
Telephone number/company
93
Service date Next service on
Maintenance interval: 1 year