Appendix
20
Installation and maintenance instructions recoVAIR 0020188110_03
Setting level
Values
Unit
Increment, select
Default
setting
Min.
Max.
Installer level
→
Configuration
→
Language
Current lan-
guage
Languages available for selection
English
Contact data
Phone number
0 - 9
Installation height
−
200
2000
m
50
100
Nominal flow
175
280
m
³
/h
5
Int. ventil. vol. flow
120
130
%
1
130
Red. ventil. vol. flow
60
80
%
1
70
Exh. air disbalance
−
20
20
%
1
5
Exh. air nom. flow corr.
−
40
40
%
1
0
Sup. air nom. fl. corr.
−
40
40
%
1
0
Exh.air int. vol. fl. cor.
−
40
40
%
1
0
Sup.air int. vol.fl. cor.
−
40
40
%
1
0
Exh. air red. vol. corr.
−
40
40
%
1
0
Sup. air red. vol. corr.
−
40
40
%
1
0
Frost prot. element
Not available
,
Electrical
,
Hydraulic
Not avail-
able
Air-earth collector
Not available
,
Available
Not avail-
able
Diff.temp. bypass
0
25
℃
0.5
10
Pressure monitor
Not available
,
Available
Not avail-
able
Step switch
Not available
,
Available
Not avail-
able
Air quality sensor
0
2
1
0
Min. CO2 content
350
600
ppm
50
450
Max. CO2 content
800
2000
ppm
50
1200
U value
0.2
2.5
W/(m
2
K)
0.1
1.5
Min. air humidity
30
40
%
2
38
Max. air humidity
50
70
%
2
68
System efficiency
On
,
Off
Off
Software version
Is displayed only
Appliance type
1
4
1
Installer level
→
Resets
→
Factory settings
Yes
,
No
No
Res. days until maint.
Yes
,
No
No
Reset exh. air ventil.
Yes
,
No
No
Reset supply air fan
Yes
,
No
No
Reset FPE
(optional)
Yes
,
No
No
Reset bypass
(optional)
Yes
,
No
No
Installer level
→
Start inst. assistant
→
Language
Languages available for selection
English
Installation height
−
200
2000
m
50
100
Nominal flow
175
280
m
³
/h
5
Exh. air nom. flow corr.
−
40
40
%
1
0
Sup. air nom. fl. corr.
−
40
40
%
1
0
1)
Fault lists are only available, and can only be deleted, if faults have occurred.