background image

 

 

open  top  sealed  with  a  cast  cover  (2).  The 
flexible disc (3) is retained by the cover. 
 
An  optional  valve  mounted  position  indicator, 
with  or  without  limit  switch,  is  available  to 
provide  local  and  remote  position  indication.  
These also can be field installed (see Page 4). 
 
An  optional  backflow  actuator  is  available  to 
manually  open  the  valve  to  allow  reverse  flow.  
The  backflow  device  can  be  easily  installed  in 
the field (see Page 5).  
 

INSTALLATION 

The  Figure  200  Rubber  Flapper  Check 
Valve  must  be  properly  installed  for  proper 
operation.  It may be installed in either horizontal 
or  vertical  (flow-up)  applications.    However, 
when horizontal, the valve must be installed with 
the nameplate facing up.  In all installations, the 
arrow cast in the valve cover must be pointed in 
the direction of forward flow.  
 
Do  not  remove  flange  protectors  until  ready  to 
install  and  ensure  there  is  no  debris  inside  the 
valve before installation.   
 
Flanged  valves  should  only  be  mated  with  flat-
faced  pipe  flanges  equipped  with  full-face 
gaskets.  
 

CAUTION 

The use of ring gaskets or mating flanges with a 

raised face may damage valve flanges. 

 
The  valve  and  adjacent  piping  must  be 
supported  and  aligned  to  prevent  imposing 
stress  on  the  valve.  Once  the  flange  bolts  or 
studs  are  lubricated  and  inserted  around  the 
flange,  uniformly  hand  tighten.  Then  tighten the 
bolts  to  the  recommended  torque  in  graduated 
steps using the cross-over tightening method.  If 

leakage  occurs,  allow  gaskets  to  absorb  fluid 
and  check  torque  and  leakage  after  24  hours. 
Do not exceed bolt rating or extrude gasket. 
 

PREVENTIVE MAINTENANCE 

The  Figure  200  Rubber  Flapper  Check  Valve 
requires 

no 

scheduled 

lubrication 

or 

maintenance.  The  valve  can  be  inspected  or 
serviced without removal from the line.  
 
Valve  Inspection:  If  internal  inspection  of  the 
valve  is  required,  follow  the  disassembly 
instructions provided below.  
    

TROUBLESHOOTING

 

Common problems and solutions are presented 
below to assist you in troubleshooting the valve 
assembly in an efficient manner. 
 

• 

Leakage at flanges  

Tighten bolts, replace gasket. 
 

• 

Valve leaks backwards when closed 

Inspect  disc  for  damage  and  replace.  Inspect 
metal seating surface; clean if necessary. 
 

• 

Valve does not open 

Check for obstruction in valve; see Disassembly 
procedure  below.    Operating  pressure  may 
be  insufficient  to  open  valve.    If  less  than  0.5 
PSIG review application with factory 
 

• 

Leakage at Backflow Actuator 

Remove  line  pressure  and  exercise  actuator.  If 
leak  persists,  replace  seals  in  actuator;  see the 
Backflow Actuator Seal Replacement Procedure 
on Page 6. 
 

DISASSEMBLY 

The valve can be disassembled for inspection or 
repair while in the line or when removed if more 
convenient.    All  work  on  the  valve  should  be 

Отзывы: