Temperature Commissioning
Note: mixed water temperature at terminal fitting should never exceed 46°C.
The valve has been factory set under balance pressures and hot water supply at 65°C.
When your specific operating conditions are significantly different from the above, the
temperature of the water may vary from the setting.
When the difference is too great, you can adjust the calibration of the valve to suit
individual requirements of the installation:
1. Check the temperature of the water being delivered from the outlet with a
thermometer, when the stop arm is located at 12 o'clock.
Note:
temperature readings should be taken at normal flow rate after allowing for the
system to stabilise.
2. If the temperature is not 38°C proceed to reset the calibration as follows:
Remove the stop adaptor.
Ensure the step on the stop ring is located at 8 o'clock.
Do not remove the plastic stop ring.
Please continue on next page.
Stop adapter
Screw
Temperature Commissioning
Turn the spline of the thermostatic valve clockwise to decrease the temperature and
anti-clockwise to increase the temperature until 38°C is achieved at outlet.
Note:
the sensing part of the thermometer probe must be fully submerged in the water
that is to be tested.
Replace the stop adaptor making sure that the stop arm is located at 12 o’clock.
When the handle is attached (see page 13) ensure the temperature does not exceed
46°C when turned entirely anti-clockwise.
Your valve setting is now commissioned.
Stop ring
Step on stop
ring located
at 8 o'clock
Stop arm
Stop
Temperature
valve spline