VADA FLOW BOSS VFB-DSU Скачать руководство пользователя страница 10

19

18

VADA FLOW BOSS 

DIGITAL WATER SWITCHING UNIT

 

VFB-DSU 

INSTALLATION MANUAL

OPERATION

Current Draw 

1.  Press the “MODE” button until “Pump 

Current” is displayed.

Current Time 

1.  Press the “MODE” button until you see the 

current time and date displayed.

ADVANCED SETTINGS 

OVERVIEW

You can enter the ‘Advanced Setting’ menu by 
holding the RESET button down for 5 seconds. 
The user can scroll through the following 
settings by pressing the “RESET” key: 

1.  Cut In Flow
2.  Cut Out Flow
3.  Minimum Pressure
4.  Maximum Run Time
5. Float/Floatless

You can exit ‘Advanced Setting’ menu anytime 
by pressing the “MODE” key.

Cut In Flow

This function is used to determine the flow rate 
at which the pump will activate (aka: cut in). 
The Cut In flow rate must be higher than the 
Cut Out flow rate.

1.  Press the “RESET” button until you reach 

“Cut In Flow”. 

2.  Press the ‘up’ or ‘down’ arrow to select the 

appropriate cut in level. 

Note:

 It is recommended the Cut In flow rate 

be 1 lpm.

Cut Out Flow 

This function is used to determine the flow rate 
at which the pump will stop (aka: cut out). 

1.  Press the “RESET” button again to select 

the “Cut Out Flow”. 

2.  Press the ‘up’ or ‘down’ arrow to select the 

appropriate cut out level.

Note: 

It is recommended the Cut-Out flow rate 

be 1 lpm.

Minimum Pressure

1.  Press the “RESET” button until you reach 

“Min Pressure”. 

2.  Press the ‘up’ or ‘down’ arrow to select the 

appropriate pressure. 

Note: 

The Min-Max pressure required for 

the switching unit is 100–1000kPa. It is 
recommended to operate the unit between 
500–750kPa.

Maximum Run Time 

This function is used to ensure that the 
pump will never over run in the event a tap is 
mistakenly left open, or a toilet cistern is leaking.

1.  Press the “RESET” button until you reach 

“Max Run Time”. 

2.  Press the ‘up’ or ‘down’ arrow to select the 

appropriate max run time. 

Float/Floatless

Important: 

It is strongly recommended  

to install a float switch in the tank. Failure to  
do so may void warranty. Please refer to page 
11
 for more detail on why installing a float 
switch is necessary for your installation.

1.  Press the “RESET” button until you reach 

“Floatless Y/N” 

2.  Press the ‘up’ or ‘down’ arrow to select 

whether the unit is Floatless or not.

Note: 

The VFB-DSU will be set to operate on 

“Float” setting by default.

Содержание FLOW BOSS VFB-DSU

Страница 1: ...DIGITAL WATER SWITCHING UNIT INSTALLATION MANUAL VFB DSU ...

Страница 2: ...ce number Product serial number Product model number A smooth day is a good day That s why Vada is dedicated to creating pump solutions that you can count on With a focus on easy selection simple installation and high quality you can hold your head high knowing your reputation is protected It s Vada Performance simplified THANK YOU Scan for set up support ...

Страница 3: ...PA 1 bar Max operating pressure 1000kPA 10 bar Minimum flow rate 1 lpm Voltage 1 230 240V 50Hz Maximum electrical load 10A 2400W IP Rating IP44 Vada strongly recommends installing the float switch supplied in the tank on site Installing a float switch prevents air from re entering the suction line and damaging your Vada product Installing a float switch also reduces build up from tank debris enter...

Страница 4: ...ion pipe internal diameter must be no smaller than 25mm x2 mesh inline filters Discharge pipe internal diameter must be no smaller than 25mm 16mm hole saw Thread tape Access to a 10A outdoor power point Inline filter AKA Y Strainer Isolation valve Swing check valve Float switch tank If the incoming mains pressure to your property is greater than the specified 1000 kPa 10 bar you MUST fit a pressur...

Страница 5: ... type of device to the entire house will extend the life of other appliances such as washing machines hot water service and dishwashers This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person respons...

Страница 6: ...pple from the union Rethread the nipple into the switching unit making sure the union nut remains on the nipple Re join the union to complete connection 6 Connect the VFB DSU to the discharge port on the pump 7 Connect the incoming mains water supply to the MAINS port on the VFB DSU This is marked MAINS with an arrow pointing out of the VFB DSU indicating water flow direction Note Brace this fitti...

Страница 7: ...pply by either a Hard wiring Local authorities may require the pump to be hard wired Important If this applies to you the electrical connection must be done by a qualified electrician with pump knowledge according to the National wiring rule AS NZS 3000 and or any local council requirements WARNING Hazardous voltage can cause shock burn or cause death The supply voltage for the Digital Water Switc...

Страница 8: ...e This indicates to the switching unit that there is no water in the tank and to switch to mains supply operation 4 Open an outlet on the household side of the VFB DSU The VFB DSU should now be allowing mains water to supply the demand 5 Close the tap and replace the float switch connection If there are any variations to these outcomes please refer to the Troubleshooting section on page 28 70mm ab...

Страница 9: ...nstallation will be random 4 To set the date and time press the Time Set button 5 Press either up or down arrow to select the correct day of the month When the correct value is observed press the Time Set button again 9 In the event the user inputs incorrect information the Invalid Data screen will appear 10 The VFB DSU has been set to its basic settings For advanced settings and additional functi...

Страница 10: ... which the pump will stop aka cut out 1 Press the RESET button again to select the Cut Out Flow 2 Press the up or down arrow to select the appropriate cut out level Note It is recommended the Cut Out flow rate be 1 lpm Minimum Pressure 1 Press the RESET button until you reach Min Pressure 2 Press the up or down arrow to select the appropriate pressure Note The Min Max pressure required for the swi...

Страница 11: ...50Hz Max electrical load 10A 2400W Power standby 3 5W Control power on 30W IP rating IP44 Min flow rate 1lpm Min mains pressure 1 bar Max operating pressure 10 bar Min max water temperature 1 C 40 C Min max ambient temperature 1 C 40 C CONNECTION Mains water supply inlet 25mm FI BSP Pump connection 25mm FI BSP Water outlet connection 25mm FI BSP TECHNICAL INFORMATION C F H I A B J G D E A 52mm B 1...

Страница 12: ...ystem will automatically default to mains water supply When power is restored the switching unit will revert to normal operation Loss of Mains Supply Water If town supply water is shut off in your area the switching unit may not be able to detect water demand in the household e g if the toilet cistern needs refilling You can override normal control and start the pump to supply water out of the rai...

Страница 13: ...lly connected Ensure that it is isolated from electrical supply during installation and any subsequent service work Unit should only be serviced by qualified personnel or licensed service agent OFF 6 If rainwater is detected the system will revert to normal operation 7 If no rainwater is detected then the switching unit will go to a further 7 day lock out as per step 4 The unit will continue to au...

Страница 14: ...k maximum run time setting OVER CURRENT Error Code 3 Over current detected measured current exceeds 10amps 1 Check pump for mechanical resistance Refer to troubleshooting in pump manual 2 Check pump motor for electrical faults Refer to troubleshooting in pump manual NO PUMP CONNECTED CHECK FUSE Error Code 4 No load detected 1 Check to make sure the pump is connected 2 Check for blown fuse on the b...

Страница 15: ...ater 3 Remove pump barrel union 4 Inspect clean replace filter Pump is not primed 1 Open gate valve and prime the pump Refer to pump manual on how to prime the pump 2 Reset the switching unit by pressing Reset key SYMPTOM CAUSE SOLUTION Pump continually runs or cycles on and off consistently over time when no outlets open Leak in the plumbing system 1 Identify where the leak is e g toilet or tap l...

Страница 16: ...atives or an authorised customer service workshop and any attempt to repair the device by the customer or unauthorised third parties shall terminate the warranty WARRANTY CONDITIONS The warranty will apply only under all the following conditions The pump has been installed by a qualified licensed personnel The pump is returned in good condition and has not arrived damaged The pump is located so th...

Страница 17: ......

Отзывы: