OPTBK AS-interface board

Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205

1.2.2

AS-i board layout and connections

Both data and power are supplied on the two-wire cable. The DC power carries the AS-interface sig-
nal. The AS-interface signal and the voltage regulating circuitry of the power supply  must be sep-
arated.

Do not ground the AS-interface negative (ASI N). Grounding the signal lines results in poor commu-
nication or completely lost communication. The typical AS-interface media is not shielded. If shield-
ing is necessary for the application, ground the shield in only one place.

The AS-interface power supply provides voltages in the 30VDC range (29.5-31.6 VDC). It is higher 
than the industry standard nominal 24VDC to compensate for the voltage drop on the line as well 
as the drop through the AS-interface IC chip.

Figure 1. OPTBK AS-interface option board.

OPTBK  AS-interface terminals 

Terminal

Signal

Technical information

1

ASI P

AS-int

2

ASI N

AS-interface -

3

ASI Supply P

Auxiliary output voltage (ASi voltage input - max 2.4V at 
maximum output current)

4

ASI Supply N

GND of Auxiliary output voltage

Table 3. OPTBK AS-Interface terminals

Содержание OPTBK

Страница 1: ...vacon ac drives optbk as interface option board user manual...

Страница 2: ......

Страница 3: ...11B Rev B Revision release date 22 5 15 1 OPTBK AS interface board 2 1 1 General 2 1 2 Technical data 2 1 2 1 AS interface technical data 3 1 2 2 AS i board layout and connections 4 1 2 3 Physical med...

Страница 4: ...expertise is necessary in the installation It has a quick Snap and Go cable penetration system The installation is easy because the AS interface has freely selectable network topology Also the configu...

Страница 5: ...s Star or Tree Topology Installation Special yellow unshielded cable with 2 wires providing data and 30 V Alternatively data and power on separate cables 100 m length per Segment extendible up to 300...

Страница 6: ...rface media is not shielded If shield ing is necessary for the application ground the shield in only one place The AS interface power supply provides voltages in the 30VDC range 29 5 31 6 VDC It is hi...

Страница 7: ...e connectors or round cable with industry standard M12 EN50 044 connectors Figure 2 AS interface Flat Cable Right figure shown with piercing teeth Figure 3 AS interface round cable with industry stand...

Страница 8: ...ion on the option board LED indications Green LED is Red LED is Meaning Note OFF OFF Power OFF No power supply available ON OFF Normal Operation Data communication is established ON ON No data exchang...

Страница 9: ...24 hour support 358 0 201 212 575 Email vacon vacon com 2 2 OPTION BOARD INSTALLATION 2 1 Vacon 100 1 Open the cover of the AC drive 2 To get access to the option board slots open the cover of the con...

Страница 10: ...ption board has a slot coding and thus it is not possible to install the option board in an incorrect slot 4 Close the cover of the control unit 5 In IP21 cut free the opening on the cover of the AC d...

Страница 11: ...358 0 201 212 575 Email vacon vacon com 2 6 Install AS interface cables and other cables 7 Close the cover of the AC drive 8 Pull the AS interface cable to the side Move the cable away from the mains...

Страница 12: ...2 vacon 10 Option board installation Tel 358 0 201 2121 Fax 358 0 201 212 205 2 2 Vacon 100 X 1 Open the cover of the AC drive 11638_00...

Страница 13: ...Option board installation vacon 11 24 hour support 358 0 201 212 575 Email vacon vacon com 2 2 To get access to the option board slots remove the screws and open the cover of the control unit 11639_00...

Страница 14: ...tion board cover 5 Remove the cable entry plate If you installed the option board in the slot D use the cable entry plate on the right side If you installed the option board in the slot E use the cabl...

Страница 15: ...oles See the Vacon 100X Installation Manual for the dimensions of the holes 7 Attach a cable gland on the hole in the ca ble entry plate Pull the AS interface cable through the hole NOTE The AS interf...

Страница 16: ...r replace option boards or fieldbus boards on an AC drive with the power switched on This may damage the boards The relay outputs and other I O terminals may have a dangerous control voltage present e...

Страница 17: ...vacon com 2 3 NOTE Incompatible boards cannot be installed on Vacon 20X Compatible boards have a slot coding that enable the placing of the board see above 4 Install the option board into the slot as...

Страница 18: ...l authoring documentation vacon com Vacon Plc Runsorintie 7 65380 Vaasa Finland Subject to change without prior notice 2015 Vacon Plc Sales code DOC OPTBK DLUK Find your nearest Vacon office on the In...

Отзывы: