CONTROL KEYPAD
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9.3.1
Monitoring menu (M1)
You can enter the Monitoring menu from the Main menu by pushing the
when
the location indication M1 is visible on the first line of the display. How to browse through the
monitored values is presented in Figure 45.
The monitored signals carry the indication V#.# and they are listed in Table 24. The values are
updated once every 0.3 seconds.
This menu is meant only for signal checking. The values cannot be altered here. For changing
values of parameters see Chapter 9.3.2.
Figure 45. Monitoring menu
Table 24. Monitored signals
Code
Signal name
Unit
Description
V1.1
Output frequency
Hz
Frequency to the motor
V1.2
Frequency reference
Hz
V1.3
Motor speed
rpm
Calculated motor speed
V1.4
Motor current
A
Measured motor current
V1.5
Motor torque
%
Calculated motor shaft torque
V1.6
Motor power
%
Calculated motor shaft power
V1.7
Motor voltage
V
Calculated motor voltage
V1.8
DC-link voltage
V
Measured DC-link voltage
V1.9
Unit temperature
ºC
Heat sink temperature
V1.10
Motor temperature
%
Calculated motor temperature. See All in One application
manual
V1.11
Voltage input
V
AI1
V1.12
Current input
mA
AI2
V1.13
DIN1, DIN2, DIN3
Digital input statuses
V1.14
DIN4, DIN5, DIN6
Digital input statuses
V1.15
DO1, RO1, RO2
Digital and relay output statuses
V1
V14
READY
Local
13.95 Hz
READY
Local
13.95 Hz
R EADY
Lo ca l
RUN
RUN
RUN
Monitor
Output frequency
FreqReference
11528_uk