70 • vacon
Control keypad
Telephone: +358-201-2121 • Fax: +358-201-212 205
7
Timeout time (P6.6.3)
The Timeout time setting defines the time after which the keypad display returns to the
Move to the Edit menu by pressing the
Menu button right
. Set the timeout time you want and confirm
the change with the
Enter button
. You can return to the previous step anytime by pushing the
NOTE: This function cannot be disabled.
Figure 7-13. Timeout time setting
7.4.6.4 Hardware
settings
In the Hardware settings submenu (S6.7) you can further customise the settings of the frequency
converter with three parameters:
Fan control, HMI acknowledgement timeout and HMI retry.
Fan control (P6.7.2)
Note! Only the higher power modules of MF3 have been equipped with a cooling fan, in lower power
modules of MF3 the cooling fan is available as optional equipment.
If the cooling fan has been installed in MF3 it runs continuously, when the power is switched on.
Sizes MF4 and bigger:
This function allows you to control the frequency converter’s cooling fan. You can set the fan to run
continuously when the power is switched on or depending on the temperature of the unit. If the latter
function has been selected the fan is switched on automatically when the heat sink temperature
reaches 60
°
C. The fan receives a stop command when the heat sink temperature falls to 55
°
C.
However the fan runs for about a minute after receiving the stop command, as well as after
changing the value from 0
(Continuous)
to 1
(Temperature).
Enter the edit mode by pushing the
. The present mode shown starts to blink. Use
the
to change the fan mode. Accept the change with the
enter
STOP
I/O term
READY
STOP
I/O term
READY
STOP
I/O term
READY
nxlk24. fh8
s
s
CANCEL
CONFIRM CHANGE