Charging can be achieved by upper system control or simply by Value ID Control functions.
Charging will start automatically when the DC/DC converter overvoltage limit is reached
even without charging reference.
•
When the grid converter power flow is parallel to the grid, the DC-Link voltage will go down
until it reaches the DC/DC converter undervoltage level, where the voltage remains until the
DC/DC converter discharging current limit is reached.
Figure 36. Charging and discharging
•
AFE-operation mode.
o Not practical. Could be possible when DC/DC operated with under voltage control with a
drooping. But DC reference changes makes steep power changes.
•
Island-operation mode
o Power control not possible, drive will give to the grid what the grid needs.
o Cannot operate parallel with other power sources.
o Makes a grid but cannot synchronize to an existing one.
DC
OV Level
uG
OV Level
uG
UV Level
DC
UV Level
Discharging
Controlled charging possible
Current limit charging