background image

VACON CX 

Profibus user’s manual

  

Page 

24

 

________________________________________________________________________________________ 

________________________________________________________________________________________ 
Vacon Oyj 

Phone +358-201-2121      

Fax: +358-201-212 205 

APPENDIX B 

Special Actual Values 

 

By default, the 

Actual Value

 corresponds to the motor rotation speed in percentage.  

Actual Value

 can be attached some other monitored variable. Meaning of 

Actual Value

 can be selected 

by resetting a Control Word bits 15...11. The user can choose to show one of the monitoring page 
variables or the active fault code. 
Control Word (bits 15...11) is binary coded as follows: 
 

Control Word 

Description 

bit 15 

bit 14 

bit 13 

bit 12 

bit 11 

 

Default, Actual Speed (%)  

0 0 0 0 1 

V1 

(see 

table 

0-1) 

0 0 0 1 0 

V2 

(see 

table 

0-1) 

0 0 0 1 1 

V3 

(see 

table 

0-1) 

 

 

 

 

 

 

 

 

 

 

1 1 1 0 1 

V29 

(see 

table 

0-1) 

1 1 1 1 0 

Active 

Fault 

Code 

1 1 1 1 1 

Default, 

Actual 

Speed 

(%) 

 

NOTE: The minimum interval allowed to change the bits above is 500ms! 

 

Data name 

Step 

Unit 

Description 

V1 

Output frequency 

0,01 

Hz 

Frequency to the motor 

V2 

Motor speed 

rpm 

Calculated motor speed 

V3 

Motor current 

0,1 

Measured motor current 

V4 

Motor torque 

Calculated actual torque/nominal torque of  the 
unit 

V5 

Motor power 

Calculated actual power/nominal power of  the 
unit 

V6 

Motor voltage 

Calculated motor voltage 

V7 

DC-link voltage 

Measured DC-link voltage 

V8 

Temperature 

°C 

Temperature of the heat sink 

V9 

Operating day count 

 

DD.dd Operating days 1), not resetable 

V10  Operating hours, "trip 

counter” 

 HH.hh Operating hours 2), can be reset with program-

button #3 

V11  MW-hours 

0,001 

MWh  Total MW-hours, not resetable 

V12 MW-hours, 

"trip 

counter" 

0,001 

MWh  MW-hours, can be reset with programmable 

button #4 

V13 Voltage/analogue 

input 

0,01 

Voltage of the terminal Uin+ (control board) 

V14 Current/analogue 

input 

0,01 

mA 

Current of terminals Iin+ and Iin- (control board) 

V15  Digital input status, 

gr. A 

 

 

0 = Open Input, 1 = Closed Input (Active) 

V16  Digital input status, 

gr. B 

 

 

0 = Open Input, 1 = Closed Input (Active) 

V17  Digital and relay 

output status 

 

 

0 = Open Input, 1 = Closed Input (Active) 

V18  Control program 

 

 

Version number of the control software 

V19  Unit nominal power 

0,1 

kW 

Shows the power  size of  the unit 

V20 Motor 

temperature 

rise 

100%= temperature of motor has risen to nominal 
value 

 

 

 

 

 

 

 

 

1)

 DD = full days, dd = decimal part of a day 

 

 

 

 

 

 

 

2)

 HH = full hours, hh = decimal part of an hour

 

Содержание CXL

Страница 1: ...VACON CX CXL CXS FREQUENCY CONVERTERS Profibus DP Fieldbus Option Board USER S MANUAL Subject to changes without notice F O R S M O O T H C O N T R O L ...

Страница 2: ...NS 9 5 1 Board layout 9 5 2 Profibus connections 9 5 3 I O control connections 10 6 COMMISSIONING 11 7 PROFIBUS VACON CX INTERFACE 12 7 1 General 12 7 2 PPO types 12 7 3 Process Data 15 7 3 1 Control Word 15 7 3 2 Status Word 16 7 3 3 State Machine 16 7 3 4 Speed Reference 17 7 3 5 Actual Value 18 7 3 6 PD1 PD4 18 7 4 Parameter Data 19 7 4 1 Actual Values 19 7 4 2 Parameter Read and Write 20 7 4 3...

Страница 3: ...s instructed in this manual Note that the installation procedure is different for CX CXL board CX202OPT and CXS frequency converters CX210OPT The control connections are isolated from the mains potential and the I O ground is connected to the frame of the device via a 1 MΩ resistor and 4 7 nF capacitor The control I O ground can also be connected directly to the frame by changing the position of t...

Страница 4: ...cs Rtrip 4 7 kΩ Encoder input 3 pcs 24 V 0 10 V 1 18 V Ri 3 3 kΩ 5 V 0 2 V 1 3 V Ri 330 Ω Aux voltage 24 V 20 max 50 mA Safety Fulfils EN50178 standard Communication mode Profibus DP PPO types 1 2 3 4 Communication parameters Address Baud Rate 1 to 127 9 6 kBaud to 12 MBaud Table 2 1 Profibus communication data 2 2 Profibus cable Profibus devices are connected in a bus structure Up to 32 stations ...

Страница 5: ...ble 2 2 Line Parameter Baud rate kbit s 9 6 19 2 93 75 187 5 500 1500 3000 12000 Length line A m 1200 1200 1200 1000 400 200 100 Length line B m 1200 1200 1200 600 200 Table 2 3 Line length for different transmission speeds Following cables can be used e g Belden Profibus Data Cable 3079A Olflex Profibus Cable 21702xx Siemens SINEC L2 LAN cable for profibus 6XV1 830 0AH10 Cabling Bus Termination R...

Страница 6: ...sive and complex communication tasks PROFIBUS specifies the technical and functional characteristics of a serial fieldbus system with which decentralized digital controllers can be networked together from the field level to the cell level PROFIBUS distinguishes between master devices and slave devices Master devices determine the data communication on the bus A master can send messages without an ...

Страница 7: ... can also be connected to terminal X6 if the power cable from the power board is connected to terminal X5 C Bend the data cable into an S curve as far as possible from the power board transformer 4 before you place the plastic board above the control board D Remove the protection foil of the plastic board and place the plastic board on the control board remember the right position of the plastic b...

Страница 8: ..._______________________________ ________________________________________________________________________________________ Vacon Oyj Phone 358 201 2121 Fax 358 201 212 205 Plastic board Control board 11 7 4 6 3 8 9 12 10 2 1 5 Figure 4 1 Fieldbus board installed onto the control board Fieldbus board ...

Страница 9: ...ON Directly to the frame of the device OFF To the frame of the device via RC filter Diagnostic LED H1 Data Exchange state for Profibus DP Red The red LED goes out when communication is established H1 led is active when Fieldbus board is not ready to exchange data H3 Supply Voltage Green H3 led is active if the Fieldbus board has supply voltage 5 2 Profibus connections Screw Connector connector X5 ...

Страница 10: ...disabled 211 DIE3 Acceler Decel time selection Contact open time 1 selected Contact closed time 2 selected 212 DIE4 Jogging speed selection Contact open no action Contact closed jogging speed 213 Not Used 214 DIE6A 215 DIE6A Pulse input A differential input 216 DIE7B 217 DIE7B Pulse input B differential input 90 degrees phase shift compared to pulse input A 218 DOE1 Encoder direction output 219 DO...

Страница 11: ...selected Parameter P0 1 0 For further information about use of parameters see Vacon CX CXL CXS User s Manual Chapter 7 Start up test FREQUENCY CONVERTER APPLICATION 1 Check that the control panel is not the active control source See Vacon CX CXL CXS frequency converter User s manual Chapter 7 2 Set parameter Fieldbus control select to value 1 On MASTER SOFTWARE 1 Set Control Word value to 0hex 2 S...

Страница 12: ...o the master The contents of Input Output data is defined in a device profile PROFIDRIVE is the device profile for frequency converters The Vacon CX frequency converter can be controlled by Profibus DP master using PPO types defined in PROFIDRIVE see next chapter When fieldbus has been selected as the frequency converter s active control place the frequency converter s operation can be controlled ...

Страница 13: ...quest rejected fault code Fault Number if response 7 Fault Number Description 0 Illegal Parameter 1 Parameter is read only e g actual values 2 Parameter value is out of limits 17 Request temporarily rejected e g can be changed only for STOP state 18 Other fault 101 Unknown request type Example1 PPO1 mode Read parameter number 102 Par 1 2 Start frequency converter and set speed reference 50 00 Comm...

Страница 14: ... to parameter number 701 Par 7 1 value 2 Keep Run mode on and Send speed reference 75 00 Command Master Slave ID 22BD hex 2 Write parameter value 2BD Parameter 701 Response to reference fault IND 0000 hex 0000 No meaning VALUE 0000 0002 hex 0000 0002 Parameter value CW 047F hex 04 7F Start command see chapter control word and state machine REF 1D4C hex Speed ref 75 00 37 50 Hz if parameter min fre...

Страница 15: ... PD1 Variables B PD2 U PD3 S PD4 Active Fault Code D P M RUN STOP A DIRECTION S FAULT RESET T E Frequency Reference R Frequency Reference 2 Input CONTROL SOURCE Status Word READY STATE Actual Value RUN STATE PD1 DIRECTION STATE PD2 FAULT STATE PD3 PD4 Output Frequency 7 3 1 Control Word The Control command for the state machine see figure 7 1 The state machine describes the device status and the p...

Страница 16: ...tial READY 1 Not Ready READY 2 DISABLE ENABLE 3 NO FAULT FAULT ACTIVE 4 STOP 2 OFF STOP 2 ON 5 STOP 3 OFF STOP 3 ON 6 START ENABLE START DISABLE 7 No Warning Warning 8 Reference Actual value Reference Actual value 9 Fieldbus control OFF Fieldbus control ON 10 Not used Not used 11 Not used Not used 12 FC stopped Running 13 Not used Not used 14 Not used Not used 15 Not used Not used 7 3 3 State Mach...

Страница 17: ...of frequency area between set minimum and maximum frequency 10000 100 00 Direction reverse 0 0 00 Direction forward 10000 100 00 Direction forward DISABLE INIT Bit6 1 Reset fault Bit7 0 xxxx x1xx xxxx x110 Bit7 1 Bit0 0 Fault Bit0 1 Bit3 1 Bit4 1 Bit5 1 Bit6 1 Power ON READY 1 STOP Bit0 1 READY 2 STOP Bit1 1 ENABLE STOP Bit2 1 RUNNING RUN NOT READY STOP Bit6 0 Bit0 0 FAULT ACTIVE FAULT Bit3 1 Bit1...

Страница 18: ...can read the frequency converter s actual values using process data variables There are four process data variables and each of them can be selected to show one of the monitoring page variables or active fault code Selection can be done in two different ways By master Parameter 916 1 PD1 916 2 PD2 916 3 PD3 916 4 PD4 By control panel Parameter Process Data 1 PD1 Process Data 2 PD2 Process Data 3 P...

Страница 19: ...e read and parameters can be read and written using PPO types 1 and 2 7 4 1 Actual Values Actual Values can be read by using the parameter read function Profibus parameter numbers according to monitored item numbers are as follows Parameter number Vacon variable 1 n1 2 n2 98 n98 Number Data name Step Unit Description V1 Output frequency 0 01 Hz Frequency to the motor V2 Motor speed 1 rpm Calculate...

Страница 20: ...e power size of the unit V20 Motor temperature rise 1 100 temperature of motor has risen to nominal value Table 7 1 Monitored Items 1 DD full days dd decimal part of a day 2 HH full hours hh decimal part of an hour For Special Actual Values see Appendix B 7 4 2 Parameter Read and Write The Vacon variables and parameters can be read and written using the Parameter Read Write function Profibus param...

Страница 21: ... in Vacon CX Profibus DP Master is not active and the control source is fieldbus Check the system Master device UL led is not active Supply Voltage Green The power cable connection between control board and fieldbus board is not working Check the installation if installation is correct contact the nearest Vacon distributor DE led is active Data Exchange not Ready and actual value n22 0 DE led is a...

Страница 22: ...supp 1 19 2_supp 1 93 75_supp 1 187 5_supp 1 500_supp 1 1 5M_supp 1 3M_supp 1 6M_supp 1 12M_supp 1 MaxTsdr_9 6 60 MaxTsdr_19 2 60 MaxTsdr_93 75 60 MaxTsdr_187 5 60 MaxTsdr_500 100 MaxTsdr_1 5M 150 MaxTsdr_3M 250 MaxTsdr_6M 450 MaxTsdr_12M 800 Redundancy 0 Repeater_Ctrl_Sig 0 24V_Pins 0 Implementation_Type Profibus for Vacon CX Freeze_Mode_supp 1 Sync_Mode_supp 1 Auto_Baud_supp 1 Set_Slave_Add_supp...

Страница 23: ... not ready to exchange data H3 Supply Voltage Red H3 led is active if the Fieldbus board has supply voltage Profibus connections Screw Connector connector X5 Terminal resistors not included in the package Signal Connector X5 Description Shield X5 1 Cable shield VP X5 2 Supply voltage of the terminating resistance RxD TxD P X5 3 Receive Transmission data positive B RxD TxD N X5 4 Receive Transmissi...

Страница 24: ...1 rpm Calculated motor speed V3 Motor current 0 1 A Measured motor current V4 Motor torque 1 Calculated actual torque nominal torque of the unit V5 Motor power 1 Calculated actual power nominal power of the unit V6 Motor voltage 1 V Calculated motor voltage V7 DC link voltage 1 V Measured DC link voltage V8 Temperature 1 C Temperature of the heat sink V9 Operating day count DD dd Operating days 1 ...

Страница 25: ...rd The power cable can also be connected to terminal X6 if terminal X5 is already reserved by the power cable from the power board D Remove the protective foil of the plastic board and place the plastic board above the control board Be sure to place the plastic board correctly so that the stand sleeve 4 comes out through the hole on the board E Place the board on the protective plastic board 6 and...

Страница 26: ...___________________________________________________ Vacon Oyj Phone 358 201 2121 Fax 358 201 212 205 G Connect the power cable 5 to terminal X9 on the option board H Attach the control panel base with four screws I Check the connections Remove all foreign objects from inside the frequency drive Put the control panel and the frequency drive cover back to their places ...

Страница 27: ...Vacon Oyj P O Box 25 Runsorintie 7 FIN 65381 VAASA FINLAND Phone 358 201 2121 Fax 358 201 212 205 ud188g doc 13 5 2002 ...

Отзывы: