6. COMMISSIONING
READ FIRST THE COMMISSIONING OF THE FREQUENCY CONVERTER IN VACON CX/CXL/CXS
FREQUENCY CONVERTER USER'S MANUAL (CHAPTER 8.)
Commissioning of the Fieldbus board:
Check that Multi-purpose Control Application II (or e.g. Fieldbus Application) is selected.
- Parameter P0.1 = 0
For further information about use of parameters, see Vacon CX/CXL/CXS User's Manual, Chapter 7.
Start-up test:
FREQUENCY CONVERTER APPLICATION
1. Check that the control panel is not the active control source.
(See Vacon CX/CXL/CXS frequency converter User's manual, Chapter 7.)
2. Set parameter “Fieldbus control select” to value 1(On).
MASTER SOFTWARE
1. Set Control Word value to
0hex
.
2. Set Control Word value to
47Fhex
.
3. Frequency converter status is RUN
4. Set Reference value to
5000
(=50,00%).
5. The Actual value is 5000 and the frequency converter output frequency is 25,00 Hz
6. Set Control Word value to
7Dhex
.
7. Frequency converter status is STOP
If Status Word bit 3 = 1 Status of frequency converter is FAULT.