Vacon
Page 9 (15)
I/O-expander board installation (Vacon CXS-range)
Vacon Plc
Tel:
+358-201 2121
Fax:
+358-201 212 205
Service:
+358-40-8371 150
E-mail:
[email protected]
http://www.vacon.com
Connect the communication cable
(9)
to the I/O-expander board
X15 terminal
(12)
. Earth the communication cable to the option box
ground.
X15
14
15
Connect the necessary control signals. If a fieldbus board is in use, see separate manual for
more specific information.
X8
16
If an encoder input (closed loop control) is to
be used and the encoder works at a 5V level,
move three jumpers from terminal X5 to terminal
X8. If the encoder works at 24V, then terminal
X8 should be left free.
Check the connections and make sure that there are no foreign objects inside the option box.
Before connecting the mains make sure that the cover of the option box and frequency con-
verter are closed.
Set the parameters of I/O-expander board according to the Vacon "Five in One+" -applica-
tion manual (parameter group 3).
17
18
Table 3-2.
I/O-expander board installation.