ELECTRICAL CONNECTION
vacon • 26
24-hour s358 (0)201 212 575 • Email: [email protected]
5
Figure 19.Inverter connection to solar panels (units below NXV0800)
Figure 20.Inverter connection solar panels (units above and including
NXV0800)
Table 6. Panel input cable dimensions
Model
Minimum cross section
Recommended cross section
Maximum cross section
NXV0125
3x 2x70mm
2
3x 2x95mm
2
4x 2x185mm
2
NXV0200
4x 2x95mm
2
4x 2x95mm
2
4x 2x240mm
2
NXV0400
8x 2x95mm
2
8x 2x95mm
2
20x 2x185mm
2
NXV0600
12x 2x95mm
2
12x 2x95mm
2
20x 2x185mm
2
Make the solar
panel connection here
DC+
DC-
DC+
DC-
Connect one cable on either
side of the terminal bar
PE PE
PE
PE
PE
PE
Connect one cable on either side
of the term inal bar.
Make the solar panel
connection here.
DC+
DC-
DC-
DC+