ELECTRICAL CONNECTION
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Figure 18. Main cabling with optional AC-section
The cable cross section will be determined according to the power and distance to the connection
point, following the local regulations.
5.2.3
Connection to photovoltaic panels
Run the solar panel cables to the respective terminals on the drive through the bottom of the
supply unit (see Figure 5-6 left). Check for the cable sizes and the appropriate number of cables in
tables on page 25. Always connect the two cables on both sides of the terminal bar (see Figure 5-6
right).
Connect the positive pole of the photovoltaic panel to the terminal marked with ‘+’ and the negative
pole to the terminal marked with ‘-‘.
Model
Minimum cross section
per unit
[mm
2
]
Maximum cross section
per unit
[mm
2
]
All
10
240
Remember
that photovoltaic panels produce a current while they are illuminated. Be
sure to check that cables are not live.
NOTE!
Wrongly connected cables may damage the equipment.
9000.emf
13006.emf