4.4 Dynamic Braking
The Vacon 50X AC drive is supplied with an integrated dynamic braking (DB) resistor, and is designed to
have adequate dynamic braking for most applications. In cases where short stopping times or high inertia
loads require additional braking capacity, install an external resistor.
NOTE: External braking cannot be added to Size 0 models. For Size 4 (45–75 kW) and Size 5 (90–
150 kW) models, additional external dynamic braking requires a kit that provides the connec-
tions to the braking transistors. The XDBKITS4 and XDBKITS5 kits can be purchased through
VACON.
•
Starting from size 1 the internal DB resistor can be replaced by an external DB
resistor.
•
The terminal identifications of the DB resistor are “B+” and “DB”.
•
On the size 1 the DB resistor is connected by fast-on terminals 6.35 mm (see Figure
9 on page 28).
•
Starting from size 2 the DB resistor is connected by 2 separate terminals (see
Figure 3 on page 29). The internal DB resistor is connected by fast-on terminals “J3/
DB” and “J4/B+”, which are placed on the power board (right and left side of the
display).
To install an external resistor, first disconnect the internal DB resistor and properly terminate the wires
leading to it. Connect now the external resistance over the connections planned for it.
Changes to Parameter 410 must be made when using external DB resistors.
Verify with the manufacturer of the selected resistor that the resistor is appropriate for your application.
Contact VACON Application Engineering for further assistance with other possible sizing limitations.
Refer to Table 9 below for information about dynamic braking capacity for each Vacon 50X model.
Model
kW
Standard
Resistance
(
Ω
)
Standard
DB %
of Drive
Min. Allowed
Res. (
Ω
)
Max. Peak
Watts
Max. Ext. DB %
of Drive
0004 2
0,75
125
164%
125
1,223
164%
0007 2
1,5
125
82%
125
1,223
82%
0010 2
2,2
125
55%
125
1,223
55%
0015 2
4,0
60
68%
43
3,555
95%
0022 2
5,5
60
45%
30
5,096
91%
0028 2
7,5
60
34%
27
5,662
76%
0042 2
11
60
23%
20
7,644
68%
0054 2
15
30
34%
10
15,288
102%
0068 2
18,5
30
27%
10
15,288
82%
0002 5
0,75
500
163%
270
2253
302%
0004 5
1,5
500
82%
270
2253
151%
0005 5
2,2
500
54%
270
2253
101%
0009 5
4,0
120
136%
100
6084
163%
0012 5
5,5
120
91%
75
8112
145%
0016 5
7,5
120
68%
75
8112
109%
0023 5
11
120
45%
57
12944
116%
0031 5
15
120
34%
47
12944
87%
0037 5
18,5
120
27%
47
12944
69%
0043
22
120
23%
39
15600
70%
Table 9:Vacon 50X Dynamic Braking Capacity
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......