vacon 500x parameters
vacon
z
88
7
803 PWM Frequency
Default: 3.0 kHz
Range: 0.6-16.0 kHz
Level 2
The PWM Carrier Frequency parameter sets the carrier frequency of the Pulse-Width Modulation (PWM)
waveform supplied to the motor. Low carrier frequencies provide better low-end torque, but produce some
audible noise from the motor. Higher carrier frequencies produce less audible noise, but cause more
heating in the drive and motor.
804 Display Mode
Default: Std Disply
Range: n/a
Level 2
The Display Mode parameter determines how the reference or output of the drive will be displayed to the
user. If User Units is selected, parameter 805 allows you to customize the 3 unit values on the display. The
following data values may be assigned to this parameter:
Parameter Value
Description
Std DisplyStandard commanded frequency
Out FreqOutput frequency actually sent to the motor
Stator FreqFrequency of the stator
User UnitsCustom units display based on values in parameter 805
RPM UnitsCustom speed display with RPM as units
GPM UnitsCustom speed display with GPM as units
FPM UnitsCustom speed display with FPM as units
MPM UnitsCustom speed display with MPM as units
PSI UnitsCustom speed display with PSI as units
Degrees CCustom display with degrees C
Degrees FCustom display with degrees F
Time hrsCustom display time in hours of operation
Time minCustom display time in minutes of operation
Time secCustom display time in seconds of operation
Fbk RPMDisplay is scaled to read in RPM based on the PID feedback input to an analog input
Fbk PSIDisplay is scaled to read in PSI based on the PID feedback input to an analog input
Fbk GPMDisplay is scaled to read in GPM based on the PID feedback input to an analog input
Fbk UserDisplay is scaled to read in User units (parameter 805) based on PID feedback input to an analog input
Vin1 UserAn alphanumeric, 3-character value defined by the user.
Vin2 UserAn alphanumeric, 3-character value defined by the user.
Cin UserAn alphanumeric, 3-character value defined by the user.
805 Display Units
Default: RPM: 1
Range: n/a
Level 2
This parameter determines the three-character customer display units used when parameter 804 is set to
User Units. The last digit indicates the number of decimal places to be shown on the display. Up to three
decimal places are possible.
809 Display Scale
Default: 18000
Range: 1-32767
Level 2
This parameter determines how the reference or output of the drive will be displayed to the user. It selects
the maximum scaling of the display when running at maximum frequency.
810 Language
Default: English
Range: 1-65535
Level 2, Macro
This parameter configures the language text strings will be displayed in. The following data values may be
assigned:
Parameter Value
English
Spanish
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......