UL STANDARDS ON CABLING

To obey the UL (Underwriters Laboratories) 
regulations, use a UL-approved Class 1 
copper wire with a minimum heat 
resistance of +158 or +167 °F (+70 or +75°C).
You can use the drive on a circuit that gives 
a maximum of 50 000 rms symmetrical 
amperes, and a maximum of 500 V AC, 
when the drive is protected by Class T and 
J fuses.

CABLE AND FUSE SIZES, 
NORTH AMERICA

The recommended fuse types are class 
T (UL & CSA). The fuse voltage rating 
should be selected according to the supply 
network. The final selection should be 
made according to local regulations, 
cable installation conditions and cable 
specifications. Bigger fuses than those 
recommended below shall not be used.
Check that the fuse operating time is less 
than 0.4 seconds. Operating time depends 
on used fuse type and impedance of the 
supply circuit. Consult the factory about 
faster fuses. VACON® also recommends 
for high speed J (UL & CSA) fuse ranges.

THE TECHNICAL DATA OF THE VACON

®

 20 X AC DRIVE

VACON

® 

20 X AC DRIVES

INSTALLATION 

IN US AND CANADA

Download and read VACON

®

 20 X Installation Manual, 

wall-mounted drives at:

http://drives.danfoss.com/knowledge-center/ 

technical-documentation/

The dimensions of the cables must agree 

with the requirements of the UL508C.

• The cables must be PVC-isolated.
• The maximum ambient temperature 

is +104 °F (+40°C).

• The maximum temperature of the 

cable surface is +158 or +167 °F 
(+70 or +75°C).

• Use only cables with a concentric 

copper shield.

• The maximum number of parallel 

cables is 9.

When you use parallel cables, make sure 
that you obey the requirements of the 
cross-sectional area and the maximum 
number of cables.
For important information on the 
requirements of the grounding conductor, 
see the UL508C.
For the correction factors for each 
temperature, see the instructions of the 
UL508C.

QUICK GUIDE

DPD01821B

Technical item or function

Technical data

Mains 

connection

Input voltage Uin

3AC 208…240V 

1AC 208...240V 

3AC 380...480V

Input voltage tolerance

-15%…+10% continuously

Input frequency

50/60 Hz

Input frequency tolerance 45…66 Hz
Protection class

I

Connection to mains

Once per minute or less

Starting delay

4 s

Supply network

IT and TN-networks 

(cannot be used with corner earthed 

networks)

Short-circuit current

Maximum short-circuit current 

has to be <50kA

DC connection

Available as standard in 

MU2 single-phase frames and MU3

Motor 

connection

Output voltage

3AC 0…Uin

Rated output current

IN: Ambient temperature max. +40°C

Overload output current

1.5 x IN (1 min/10 min)

Starting current

IS for 2 s every 20 s (IS = 2.0 * IN)

Output frequency

0…320 Hz

Frequency resolution

0.01 Hz

Protection class

I

Motor characteristics

AC squirrel cage motors 

Permanent magnet motors

Cable type

Screened motor cable

Cable maximum length

30 m

Control 

characteristics

Switching frequency

Programmable 2…16 kHz; 

Default 6 kHz. 

Automatic switching frequency 

derating in case of overheating

Frequency reference: 

Analogue input 

Panel reference

Resolution ±0.05% (11-bit), 

accuracy ±1% Resolution 0.01 Hz

Field weakening point

8…320 Hz

Acceleration time

0.1…3000 sec

Deceleration time

0.1…3000 sec

Braking

Brake chopper standard in all three-phase 

frames. External brake resistor optional.