Technical data
vacon • 69
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
Directives
EMC
2004/108/EC
Low Voltage Directive
2006/95/EC
RoHS
2002/95/EC
WEEE
2012/19/EC
Standards
Immunity
EN61800-3 (2004), 1
st
and 2
nd
environment
Emissions
EN61800-3 (2004), Category C2
The drive can be modified for IT-networks.
THD
EN61000-3-12 (see chapter 1.9)
Safety
EN 61800-5-1
Production quality
ISO 9001
Approvals
Functional Safety
TÜV - Tested
Electrical Safety
TÜV - Tested
EMC
TÜV - Tested
USA, Canada
cULus approval, file number E171278
Declaration of
Conformity
Korea
KC mark
Australia
RCM Declaration of Conformity
Registration number E2204
Europe
EC Declaration of Conformity
Protections
Undervoltage trip limit
Depends on supply voltage (0.8775*supply volt-
age):
Supply voltage 240 V: Trip limit
211 V
Supply voltage 400 V: Trip limit
351 V
Supply voltage 480 V: Trip limit
421 V
Overvoltage fault protec-
tion
Yes
Earth fault protection
Yes
Mains supervision
Yes
Motor phase supervision
Yes
Overcurrent protection
Yes
Unit overtemperature
protection
Yes
Motor overload protec-
tion
Yes. These devices provide motor overload protec-
tion at 105% of full load amperes.
Motor stall protection
Yes
Motor underload protec-
tion
Yes
Short-circuit protection
of +24V and +10V refer-
ence voltages
Yes
Thermal motor protec-
tion
Yes (by PTC)
DC-link absolute maxi-
mum voltage
Supply voltage 240 V: absolute maximum 450V
DC
Supply voltage 400 V: 900V
DC
Table 33. VACON
®
100 X technical data.